400 V, 50 Hz VFD fan

A 400 V fan motor runs at 75% speed for 6,000 h/year. Starting current is limited to 1.2 times FLA.

Inputs

Motor nameplate
Use 0 for the code range midpoint, or the lower bound for open-ended Code V.
Starter & bus
Centrifugal duty

Starting voltage dip and cubic power

50 Hz · MetricEdit inputs
Starting voltage dip and cubic power at 50 Hz FULL LOAD100.93ALOCKED ROTOR644.11AVOLTAGE DIP0.64%ENERGY SAVED208.6KkWhBus voltage during startingNominal bus400 VEstimated during start397.44 VStarting demand83.9 kVACentrifugal affinity curve100% power0% speed100% speedVoltage dip0.64%8% budget

Detailed results
Mechanical shaft rating
55.93 kW
Baseline electrical power
60.14 kW
Estimated full-load line current
100.93 A
Inrush ratio used
5.95 kVA/hp
Nominal DOL locked-rotor current
644.11 A
Code band lower current
606.22 A
Code band upper current (exclusive)
682 A
Selected starting current
121.12 A
Starting apparent power
83.91 kVA
Bus short-circuit capacity
13.04 MVA
Bus voltage dip
0.64%
Reduced-speed electrical power
25.37 kW
Baseline energy per year
360,822.52 kWh
Reduced-speed energy per year
152,222 kWh
Annual energy savings
208,600.52 kWh
Annual energy cost savings
43,806.11 EUR/yr

Worked calculation

The predicted reduced-speed input is 0.75³ = 0.421875 of baseline power. Multiply the power difference by 6,000 hours and apply the entered energy tariff.

Reduced-speed electrical power
25.37 kW
Annual energy savings
208,600.52 kWh
Annual energy cost savings
43,806.11 EUR/yr

Values in this solution use the original example inputs.

Formulas & assumptions

Nameplate and inrush

I_FLA = 1000 · kW_shaft / (√3 · V_LL · η · PF), SKVA_DOL = hp · (kVA/hp)

Use operating-frequency nameplate data. Bounded NEMA codes use the midpoint of their interval. Code V has no upper bound. The measured inrush ratio can supersede the estimate.

Starter and source dip

Dip (%) = 100 · SKVA / (SKVA + 1000 · MVA_sc)

DOL uses the full code estimate. Wye-Delta uses one-third of DOL line current for a Delta-running motor. Soft starter and VFD inputs set modeled current in multiples of FLA. For the transformer-only source, MVA_sc = transformer kVA / (1000 · %Z/100).

Centrifugal affinity law

P₂ = P₁ · (N₂/N₁)³, ΔkWh = (P₁ − P₂) · annual hours

Assumes the same operating hours, friction-dominated duty and unchanged efficiency, with drive losses excluded. Run this part for variable-torque pumps and fans with minimal static head.

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.

Engineering references

More worked examples