Open-ended NEMA Code V

A 15 hp 230 V motor has a Code V nameplate and limited inrush documentation.

Inputs

Motor nameplate
Use 0 for the code range midpoint, or the lower bound for open-ended Code V.
Starter & bus
Centrifugal duty

Starting voltage dip and cubic power

60 Hz · US customaryEdit inputs
Starting voltage dip and cubic power at 60 Hz FULL LOAD33.56ALOCKED ROTOR843.43AVOLTAGE DIP10.67%ENERGY SAVED0kWhBus voltage during startingNominal bus230 VEstimated during start205.45 VStarting demand336 kVACentrifugal affinity curve100% power0% speed100% speedVoltage dip10.67%8% budget
  • Code V is open-ended. LRA uses the lower bound until a nameplate or test value is entered.
  • Estimated starting dip exceeds the entered voltage-dip budget.

Detailed results
Mechanical shaft rating
11.19 kW
Baseline electrical power
11.9 kW
Estimated full-load line current
33.56 A
Inrush ratio used
22.4 kVA/hp
Nominal DOL locked-rotor current
843.43 A
Code band lower current
843.43 A
Code band upper current (exclusive)
Unavailable
Selected starting current
843.43 A
Starting apparent power
336 kVA
Bus short-circuit capacity
2.81 MVA
Bus voltage dip
10.67%
Reduced-speed electrical power
11.9 kW
Baseline energy per year
23,798.93 kWh
Reduced-speed energy per year
23,798.93 kWh
Annual energy savings
0 kWh
Annual energy cost savings
0 USD/yr

Worked calculation

Screen at the 22.4 kVA/hp lower bound, giving at least 336 kVA at 15 hp. Enter measured data to improve the point estimate. The code alone supplies no upper bound.

Inrush ratio used
22.4 kVA/hp
Nominal DOL locked-rotor current
843.43 A
Code band upper current (exclusive)
Unavailable

Values in this solution use the original example inputs.

Formulas & assumptions

Nameplate and inrush

I_FLA = 1000 · kW_shaft / (√3 · V_LL · η · PF), SKVA_DOL = hp · (kVA/hp)

Use operating-frequency nameplate data. Bounded NEMA codes use the midpoint of their interval. Code V has no upper bound. The measured inrush ratio can supersede the estimate.

Starter and source dip

Dip (%) = 100 · SKVA / (SKVA + 1000 · MVA_sc)

DOL uses the full code estimate. Wye-Delta uses one-third of DOL line current for a Delta-running motor. Soft starter and VFD inputs set modeled current in multiples of FLA. For the transformer-only source, MVA_sc = transformer kVA / (1000 · %Z/100).

Centrifugal affinity law

P₂ = P₁ · (N₂/N₁)³, ΔkWh = (P₁ − P₂) · annual hours

Assumes the same operating hours, friction-dominated duty and unchanged efficiency, with drive losses excluded. Run this part for variable-torque pumps and fans with minimal static head.

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.