208 V conveyor soft start

A 25 hp 208 V conveyor motor has a soft starter set to 3.5 times full-load current.

Inputs

Motor nameplate
Use 0 for the code range midpoint, or the lower bound for open-ended Code V.
Starter & bus
Centrifugal duty

Starting voltage dip and cubic power

60 Hz · US customaryEdit inputs
Starting voltage dip and cubic power at 60 Hz FULL LOAD70.2ALOCKED ROTOR523.92AVOLTAGE DIP1.74%ENERGY SAVED0kWhBus voltage during startingNominal bus208 VEstimated during start204.38 VStarting demand88.5 kVACentrifugal affinity curve100% power0% speed100% speedVoltage dip1.74%8% budget

Detailed results
Mechanical shaft rating
18.64 kW
Baseline electrical power
20.49 kW
Estimated full-load line current
70.2 A
Inrush ratio used
7.55 kVA/hp
Nominal DOL locked-rotor current
523.92 A
Code band lower current
492.69 A
Code band upper current (exclusive)
555.14 A
Selected starting current
245.71 A
Starting apparent power
88.52 kVA
Bus short-circuit capacity
5 MVA
Bus voltage dip
1.74%
Reduced-speed electrical power
20.49 kW
Baseline energy per year
81,945.04 kWh
Reduced-speed energy per year
81,945.04 kWh
Annual energy savings
0 kWh
Annual energy cost savings
0 USD/yr

Worked calculation

Use shaft kW divided by 0.91 efficiency and 0.81 PF to find full-load apparent power. Multiply FLA by 3.5. The speed-savings input stays at 100% for this conveyor.

Estimated full-load line current
70.2 A
Selected starting current
245.71 A
Annual energy savings
0 kWh

Values in this solution use the original example inputs.

Formulas & assumptions

Nameplate and inrush

I_FLA = 1000 · kW_shaft / (√3 · V_LL · η · PF), SKVA_DOL = hp · (kVA/hp)

Use operating-frequency nameplate data. Bounded NEMA codes use the midpoint of their interval. Code V has no upper bound. The measured inrush ratio can supersede the estimate.

Starter and source dip

Dip (%) = 100 · SKVA / (SKVA + 1000 · MVA_sc)

DOL uses the full code estimate. Wye-Delta uses one-third of DOL line current for a Delta-running motor. Soft starter and VFD inputs set modeled current in multiples of FLA. For the transformer-only source, MVA_sc = transformer kVA / (1000 · %Z/100).

Centrifugal affinity law

P₂ = P₁ · (N₂/N₁)³, ΔkWh = (P₁ − P₂) · annual hours

Assumes the same operating hours, friction-dominated duty and unchanged efficiency, with drive losses excluded. Run this part for variable-torque pumps and fans with minimal static head.

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.