Wye-Delta pump start

A 150 hp Delta-running 480 V pump uses open-transition Wye-Delta starting on a 1,000 kVA transformer.

Inputs

Motor nameplate
Use 0 for the code range midpoint, or the lower bound for open-ended Code V.
Starter & bus
Centrifugal duty

Starting voltage dip and cubic power

60 Hz · US customaryEdit inputs
Starting voltage dip and cubic power at 60 Hz FULL LOAD160.82ALOCKED ROTOR1.209KAVOLTAGE DIP1.97%ENERGY SAVED167.7KkWhBus voltage during startingNominal bus480 VEstimated during start470.54 VStarting demand335 kVACentrifugal affinity curve100% power0% speed100% speedVoltage dip1.97%8% budget

Detailed results
Mechanical shaft rating
111.85 kW
Baseline electrical power
118.99 kW
Estimated full-load line current
160.82 A
Inrush ratio used
6.7 kVA/hp
Nominal DOL locked-rotor current
1,208.83 A
Code band lower current
1,136.66 A
Code band upper current (exclusive)
1,281 A
Selected starting current
402.94 A
Starting apparent power
335 kVA
Bus short-circuit capacity
16.67 MVA
Bus voltage dip
1.97%
Reduced-speed electrical power
86.75 kW
Baseline energy per year
618,772.23 kWh
Reduced-speed energy per year
451,084.96 kWh
Annual energy savings
167,687.28 kWh
Annual energy cost savings
20,122.47 USD/yr

Worked calculation

Apply one-third of the Code H direct starting current for the Wye stage. Convert that line current to starting kVA and divide by starting plus short-circuit kVA.

Nominal DOL locked-rotor current
1,208.83 A
Selected starting current
402.94 A
Bus voltage dip
1.97%

Values in this solution use the original example inputs.

Formulas & assumptions

Nameplate and inrush

I_FLA = 1000 · kW_shaft / (√3 · V_LL · η · PF), SKVA_DOL = hp · (kVA/hp)

Use operating-frequency nameplate data. Bounded NEMA codes use the midpoint of their interval. Code V has no upper bound. The measured inrush ratio can supersede the estimate.

Starter and source dip

Dip (%) = 100 · SKVA / (SKVA + 1000 · MVA_sc)

DOL uses the full code estimate. Wye-Delta uses one-third of DOL line current for a Delta-running motor. Soft starter and VFD inputs set modeled current in multiples of FLA. For the transformer-only source, MVA_sc = transformer kVA / (1000 · %Z/100).

Centrifugal affinity law

P₂ = P₁ · (N₂/N₁)³, ΔkWh = (P₁ − P₂) · annual hours

Assumes the same operating hours, friction-dominated duty and unchanged efficiency, with drive losses excluded. Run this part for variable-torque pumps and fans with minimal static head.

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.