400 V, 50 Hz Wye bank

A 75 kW process line on 400 V, 50 Hz improves from 0.76 to 0.93 lagging PF with a Wye bank.

Inputs

Load & bank
Enter the three-phase short-circuit MVA at the bank. Use 0 to omit resonance screening.
Utility penalty

Reactive compensation and capacity

50 Hz · MetricEdit inputs
Reactive compensation and capacity at 50 Hz BANK SIZE34.5kVARPER PHASE686.26µFFREED KVA18.04kVAPAYBACK11.86moBefore and after correctionCorrectedOriginalTransformer capacityBefore correction98.68 kVAAfter correction80.65 kVAReleased capacity18.04 kVACurrent reduction18.3%of original

Detailed results
Reactive compensation
34.5 kVAR
Capacitance per phase
686.26 µF
Voltage across each capacitor
230.94 V
Line current reduction
18.28%
Transformer capacity freed
18.04 kVA
Apparent power before
98.68 kVA
Apparent power after
80.65 kVA
Reactive power before
64.14 kVAR
Reactive power after
29.64 kVAR
Line current before
142.44 A
Line current after
116.4 A
Monthly penalty reduction
295 EUR/mo
Simple payback
11.86 mo
Estimated parallel resonance order
Unavailable
Estimated parallel resonance frequency
Unavailable

Worked calculation

Use 400/√3 V at each Wye capacitor in the three-capacitor equation. Compare 75/0.76 and 75/0.93 to determine capacity freed.

Voltage across each capacitor
230.94 V
Capacitance per phase
686.26 µF
Transformer capacity freed
18.04 kVA

Values in this solution use the original example inputs.

Formulas & assumptions

Required reactive power

Q_C = P · [tan(acos(PF₁)) − tan(acos(PF₂))]

Active kW stays constant. Use lagging power factors with the target at least as high as the original. Upstream apparent power falls from P/PF₁ to P/PF₂.

Three equal capacitors

C_phase = Q_C · 10⁹ / (3 · 2πf · V_C²) [µF]

Use V_C = V_LL for Delta and V_LL/√3 for Wye. Wye requires three times the capacitance per phase at equal kVAR, line voltage, and frequency.

Parallel resonance

h₀ ≈ √(1000 · MVA_sc / Q_C); f₀ = f · h₀

Screen an undetuned bank on a predominantly inductive source. An alert within 0.5 of an odd order from 3 to 13 flags a case for spectrum and switching-step review. Check other orders and actual bus configurations.

Current and payback

I = 1000 · S / (√3 · V_LL), payback = installed cost / monthly penalty reduction

Enter the tariff penalty for each condition. A positive reduction with a nonzero bank is required for a simple payback. The currency selector changes units only.

Balanced sinusoidal load. Compare manufacturer voltage, step size, inrush and switching duties. Review harmonics, resonance, and light-load overcompensation before choosing a bank.