600 V board capacity recovery

A Canadian industrial shop corrects 600 kW from 0.81 to 0.97 PF at 600 V.

Inputs

Load & bank
Enter the three-phase short-circuit MVA at the bank. Use 0 to omit resonance screening.
Utility penalty

Reactive compensation and capacity

60 Hz · US customaryEdit inputs
Reactive compensation and capacity at 60 Hz BANK SIZE284.02kVARPER PHASE697.58µFFREED KVA122.18kVAPAYBACK7.13moBefore and after correctionCorrectedOriginalTransformer capacityBefore correction740.74 kVAAfter correction618.56 kVAReleased capacity122.18 kVACurrent reduction16.5%of original

Detailed results
Reactive compensation
284.02 kVAR
Capacitance per phase
697.58 µF
Voltage across each capacitor
600 V
Line current reduction
16.49%
Transformer capacity freed
122.18 kVA
Apparent power before
740.74 kVA
Apparent power after
618.56 kVA
Reactive power before
434.39 kVAR
Reactive power after
150.37 kVAR
Line current before
712.78 A
Line current after
595.21 A
Monthly penalty reduction
2,160 CAD/mo
Simple payback
7.13 mo
Estimated parallel resonance order
Unavailable
Estimated parallel resonance frequency
Unavailable

Worked calculation

Before and after correction, apparent power is 600/0.81 and 600/0.97 kVA. Divide each by √3·600 V with the kVA-to-VA factor to compare feeder amps.

Transformer capacity freed
122.18 kVA
Line current before
712.78 A
Line current after
595.21 A

Values in this solution use the original example inputs.

Formulas & assumptions

Required reactive power

Q_C = P · [tan(acos(PF₁)) − tan(acos(PF₂))]

Active kW stays constant. Use lagging power factors with the target at least as high as the original. Upstream apparent power falls from P/PF₁ to P/PF₂.

Three equal capacitors

C_phase = Q_C · 10⁹ / (3 · 2πf · V_C²) [µF]

Use V_C = V_LL for Delta and V_LL/√3 for Wye. Wye requires three times the capacitance per phase at equal kVAR, line voltage, and frequency.

Parallel resonance

h₀ ≈ √(1000 · MVA_sc / Q_C); f₀ = f · h₀

Screen an undetuned bank on a predominantly inductive source. An alert within 0.5 of an odd order from 3 to 13 flags a case for spectrum and switching-step review. Check other orders and actual bus configurations.

Current and payback

I = 1000 · S / (√3 · V_LL), payback = installed cost / monthly penalty reduction

Enter the tariff penalty for each condition. A positive reduction with a nonzero bank is required for a simple payback. The currency selector changes units only.

Balanced sinusoidal load. Compare manufacturer voltage, step size, inrush and switching duties. Review harmonics, resonance, and light-load overcompensation before choosing a bank.