Worked calculation
At zero load the output is zero and there is no modeled load loss. The 690 W core loss remains. The terminal fault estimate still uses nameplate secondary current.
- Operating total loss
- 690 W
- Operating efficiency
- 0%
- Infinite-bus symmetrical fault
- 6.01 kA
Values in this solution use the original example inputs.
Formulas & assumptions
Nominal RMS voltages, symmetric bolted fault at secondary terminals, and losses at a fixed reference temperature. Check source X/R, service voltage, impedance tolerance, downstream impedance, and contributions from motors and generators in a fault study.
Engineering references