- Primary full-load current
- 12.55 A
- Secondary full-load current
- 360.84 A
- Infinite-bus symmetrical fault
- 9.02 kA
- Finite-bus symmetrical fault
- 8.76 kA
- Infinite-bus L–L fault on three-phase supply
- 7.81 kA
- Finite-bus L–L fault on three-phase supply
- 7.58 kA
- Infinite-bus asymmetrical peak
- Unavailable
- Finite-bus asymmetrical peak
- Unavailable
- Operating efficiency
- 98.538%
- Mathematical peak efficiency load
- 54.14%
- Peak efficiency through rated load
- 98.85%
- Operating output power
- 302.4 kW
- Operating load loss
- 3,637.76 W
- Operating total loss
- 4,487.76 W
- Minimum design capacity
- 375 kVA
- Nameplate above minimum
- -75 kVA