Energized transformer with no load

A 225 kVA transformer remains energized with its downstream equipment off.

Inputs

Nameplate & source
Use 0 for infinite bus. Enter utility fault MVA at the transformer primary.
Enter the nameplate or test ratio for peak fault estimates. Use 0 if unknown.
Use 0 to assume the utility impedance has the same angle as the transformer.
Losses & loading
Use 0 to omit minimum kVA sizing.

Transformer efficiency and fault duty

60 Hz · US customaryEdit inputs
Transformer efficiency and fault duty at 60 Hz SECONDARY FLA270.63ABOLTED FAULT6.01kAEFFICIENCY0%MINIMUM KVA—Efficiency vs. loading100% efficiency0%0% load100% loadSecondary fault duty13.8 kV480 VInfinite bus6.01 kAFinite bus5.9 kANameplate loading0% load100% rated

Detailed results
Primary full-load current
9.41 A
Secondary full-load current
270.63 A
Infinite-bus symmetrical fault
6.01 kA
Finite-bus symmetrical fault
5.9 kA
Infinite-bus L–L fault on three-phase supply
5.21 kA
Finite-bus L–L fault on three-phase supply
5.11 kA
Infinite-bus asymmetrical peak
Unavailable
Finite-bus asymmetrical peak
Unavailable
Operating efficiency
0%
Mathematical peak efficiency load
51.52%
Peak efficiency through rated load
98.694%
Operating output power
0 kW
Operating load loss
0 W
Operating total loss
690 W
Minimum design capacity
Unavailable
Nameplate above minimum
Unavailable

Worked calculation

At zero load the output is zero and there is no modeled load loss. The 690 W core loss remains. The terminal fault estimate still uses nameplate secondary current.

Operating total loss
690 W
Operating efficiency
0%
Infinite-bus symmetrical fault
6.01 kA

Values in this solution use the original example inputs.

Formulas & assumptions

Rated current and capacity

I_FLA = 1000 · kVA / (g · V), kVA_min = design kW / (PF · target load fraction)

Use g = √3 and line-to-line voltage for three-phase, or g = 1 and applied winding voltage for single-phase. Select a nameplate rating and check the reserve.

Terminal bolted fault

I_sc = I_FLA / |Z_tx + Z_src|; Z_src,pu = rated kVA / utility fault kVA

The infinite-bus case sets Z_src to zero. Enter X/R to add resistance and reactance on the same base. Without X/R, the impedance magnitudes are added assuming equal angles. For a three-phase supply with equal positive and negative sequence impedance, the L–L fault is √3/2 times the three-phase fault.

Asymmetrical peak screen

i_peak ≈ √2 · I_sc · [1.02 + 0.98 · exp(−3R/X)]

Uses the combined radial terminal impedance and nominal prefault voltage. Peak values refer to the symmetrical fault results above. They omit standard voltage and equipment correction factors and are for screening.

Losses and efficiency

η = P_out / (P_out + P₀ + x² · P_cu), x_peak = √(P₀ / P_cu)

x is load fraction relative to nameplate kVA and P_out = x · rated kVA · PF. Use consistent watts. Peak efficiency occurs when modeled load loss equals core loss.

Nominal RMS voltages, symmetric bolted fault at secondary terminals, and losses at a fixed reference temperature. Check source X/R, service voltage, impedance tolerance, downstream impedance, and contributions from motors and generators in a fault study.