Transformer operating above nameplate

A 300 kVA process transformer reaches 112% load. The new design load is 270 kW with a target utilization of 80%.

Inputs

Nameplate & source
Use 0 for infinite bus. Enter utility fault MVA at the transformer primary.
Enter the nameplate or test ratio for peak fault estimates. Use 0 if unknown.
Use 0 to assume the utility impedance has the same angle as the transformer.
Losses & loading
Use 0 to omit minimum kVA sizing.

Transformer efficiency and fault duty

60 Hz · US customaryEdit inputs
Transformer efficiency and fault duty at 60 Hz SECONDARY FLA360.84ABOLTED FAULT9.02kAEFFICIENCY98.538%MINIMUM KVA375kVAEfficiency vs. loading100% efficiency94%7% load112% loadSecondary fault duty13.8 kV480 VInfinite bus9.02 kAFinite bus8.76 kANameplate loading112% load100% rated
  • The selected load exceeds nameplate kVA. Check allowable temperature rise and loading guides.

Detailed results
Primary full-load current
12.55 A
Secondary full-load current
360.84 A
Infinite-bus symmetrical fault
9.02 kA
Finite-bus symmetrical fault
8.76 kA
Infinite-bus L–L fault on three-phase supply
7.81 kA
Finite-bus L–L fault on three-phase supply
7.58 kA
Infinite-bus asymmetrical peak
Unavailable
Finite-bus asymmetrical peak
Unavailable
Operating efficiency
98.538%
Mathematical peak efficiency load
54.14%
Peak efficiency through rated load
98.85%
Operating output power
302.4 kW
Operating load loss
3,637.76 W
Operating total loss
4,487.76 W
Minimum design capacity
375 kVA
Nameplate above minimum
-75 kVA

Worked calculation

For the operating point use 1.12² times rated load loss. For future sizing, divide 270 kW by 0.90·0.80 and compare with 300 kVA.

Operating load loss
3,637.76 W
Minimum design capacity
375 kVA
Nameplate above minimum
-75 kVA

Values in this solution use the original example inputs.

Formulas & assumptions

Rated current and capacity

I_FLA = 1000 · kVA / (g · V), kVA_min = design kW / (PF · target load fraction)

Use g = √3 and line-to-line voltage for three-phase, or g = 1 and applied winding voltage for single-phase. Select a nameplate rating and check the reserve.

Terminal bolted fault

I_sc = I_FLA / |Z_tx + Z_src|; Z_src,pu = rated kVA / utility fault kVA

The infinite-bus case sets Z_src to zero. Enter X/R to add resistance and reactance on the same base. Without X/R, the impedance magnitudes are added assuming equal angles. For a three-phase supply with equal positive and negative sequence impedance, the L–L fault is √3/2 times the three-phase fault.

Asymmetrical peak screen

i_peak ≈ √2 · I_sc · [1.02 + 0.98 · exp(−3R/X)]

Uses the combined radial terminal impedance and nominal prefault voltage. Peak values refer to the symmetrical fault results above. They omit standard voltage and equipment correction factors and are for screening.

Losses and efficiency

η = P_out / (P_out + P₀ + x² · P_cu), x_peak = √(P₀ / P_cu)

x is load fraction relative to nameplate kVA and P_out = x · rated kVA · PF. Use consistent watts. Peak efficiency occurs when modeled load loss equals core loss.