API 520 / API 526
Gas load above API letter T
A large vapor relief scenario requires 3,000,000 lb/h at 260 psia inlet and 20 psia outlet.
Inputs
Reset restores this worked example. View results ↑
Screening result
Edit inputs ↓ LiveThe required effective area exceeds API 526 letter T. Verify the relief basis and evaluate a manufacturer-engineered solution.
Calculation breakdown
- Required effective area
- 146.087 in²
- API 526 letter
- Above T
- Selected API effective area
- —
- Area reserve vs selected or largest letter
- -120.087 in²
- Required percent of reference area
- 561.87 %
- Required equivalent circular bore
- 13.6383 in
- Inlet to outlet differential
- 240 psid
- Absolute outlet / inlet ratio
- 7.69 %
- Gas critical ratio
- 52.83 %
- US gas coefficient C
- 356.0604
- Napier high-pressure factor Kn
- —
- Effective reference mass flow
- 533,928.58 lb/h
- Effective reference liquid flow
- —
Worked calculation
A large vapor relief scenario requires 3,000,000 lb/h at 260 psia inlet and 20 psia outlet.
- Required effective area
- 146.087 in²
- API 526 letter
- Above T
- Required percent of reference area
- 561.87 %
No single D–T effective letter meets the calculated area. The utilization compares required area with letter T as a reference.
Calculation basis
Gas at critical flow
Check the absolute outlet-to-inlet ratio against the critical ratio. Use relieving temperature in Rankine in the customary equation. P₁ represents the actual valve inlet under relief, including the applicable overpressure and inlet losses.
W = C·Kd·P₁·Kb·Kc·A·√(M/(T·Z)) · C = 520√[k(2/(k+1))^((k+1)/(k−1))]Steam and liquid
Use Ksh = 1 for saturated steam. The Napier correction Kn applies above 1,500 psia through 3,200 psia. This screen assumes low outlet pressure for steam. The liquid equation uses US gal/min and verified correction factors.
Wsteam = 51.5·P₁·A·Kd·Kb·Kc·Kn·Ksh · Qliquid = 38·Kd·Kw·Kc·Kv·A·√(ΔP/G)API effective letter
Choose the smallest D through T area meeting the computed requirement. If the demand exceeds T, compare against T as a reference and flag the case for engineering review.
Utilization = 100 × Arequired / Areference
Use an independently established relief load and actual relieving conditions. Verify API 520 method applicability, allowable backpressure and installation, flashing or two-phase flow, valve certification, and manufacturer-rated capacity.