API 520 / API 526

Gas load above API letter T

A large vapor relief scenario requires 3,000,000 lb/h at 260 psia inlet and 20 psia outlet.

Inputs

Relieving fluid and pressure
psia
psia
lb/h
°F
lb/lbmol
Effective sizing factors

Reset restores this worked example. View results ↑

Screening result

Edit inputs ↓ Live
REQUIRED AREA 146.087 in² API LETTER Above T SELECTED AREA — UTILIZATION 561.87 % ORIFICE & VALVE Effective areaValve sectionCRITICAL GAS Orifice area headroom FAIL SCREEN 0% 100% LIMIT 150%+
146.087 in² demand / 26 in² limit

The required effective area exceeds API 526 letter T. Verify the relief basis and evaluate a manufacturer-engineered solution.

Export or share
Calculation breakdown
Required effective area
146.087 in²
API 526 letter
Above T
Selected API effective area
—
Area reserve vs selected or largest letter
-120.087 in²
Required percent of reference area
561.87 %
Required equivalent circular bore
13.6383 in
Inlet to outlet differential
240 psid
Absolute outlet / inlet ratio
7.69 %
Gas critical ratio
52.83 %
US gas coefficient C
356.0604
Napier high-pressure factor Kn
—
Effective reference mass flow
533,928.58 lb/h
Effective reference liquid flow
—
ORIGINAL PRESET

Worked calculation

A large vapor relief scenario requires 3,000,000 lb/h at 260 psia inlet and 20 psia outlet.

Required effective area
146.087 in²
API 526 letter
Above T
Required percent of reference area
561.87 %

No single D–T effective letter meets the calculated area. The utilization compares required area with letter T as a reference.

Calculation basis

  1. Gas at critical flow

    Check the absolute outlet-to-inlet ratio against the critical ratio. Use relieving temperature in Rankine in the customary equation. P₁ represents the actual valve inlet under relief, including the applicable overpressure and inlet losses.

    W = C·Kd·P₁·Kb·Kc·A·√(M/(T·Z)) · C = 520√[k(2/(k+1))^((k+1)/(k−1))]

  2. Steam and liquid

    Use Ksh = 1 for saturated steam. The Napier correction Kn applies above 1,500 psia through 3,200 psia. This screen assumes low outlet pressure for steam. The liquid equation uses US gal/min and verified correction factors.

    Wsteam = 51.5·P₁·A·Kd·Kb·Kc·Kn·Ksh · Qliquid = 38·Kd·Kw·Kc·Kv·A·√(ΔP/G)

  3. API effective letter

    Choose the smallest D through T area meeting the computed requirement. If the demand exceeds T, compare against T as a reference and flag the case for engineering review.

    Utilization = 100 × Arequired / Areference

Use an independently established relief load and actual relieving conditions. Verify API 520 method applicability, allowable backpressure and installation, flashing or two-phase flow, valve certification, and manufacturer-rated capacity.

Sources and verification scope ↗