ACI 318-19 §16.3 / §21.2 / §22.8

Loaded and supporting surfaces of equal size

The bearing patch fills the supporting surface, so its projected area cannot grow.

Edit inputs ↓

Inputs

Editable example

Contact & support
Interface steel
φBn 318.24kip
Area A₂ 144in²
Confinement 1 
Excess Pu 0kip
AnatomyDiagrammatic scale
Parameter-linked bearing drawing. Diagrammatic scale. SUPPORT SECTIONPROJECTED PLAN1V : 2H projectionA₁ 144 in²A₂ 144 in²× 1

Screening

Within screening limits
Bearing utilization81.7%
Basic bearing18.3% below the threshold
  • Projection geometryA₂ fits within the 1V:2H envelope
    Within limit
  • Concrete bearing strengthPu ≤ φBn
    Within limit
  • Interface reinforcementDowel or continuous steel area ≥ 0.005Ag
    Within limit

Concentric compression on a rectangular support with uniform depth. Check the loaded member side, eccentricity, punching, dowel development, shear friction and actual reinforcement load transfer separately.

Calculation readout
QuantityValue
Design bearing φBn318.24 kip
Supporting area A₂ used144 in²
Confinement multiplier1
Demand beyond concrete bearing0 kip
Loaded area A₁144 in²
Maximum projected area A₂144 in²
Permitted side projection0 in
Nominal bearing Bn489.6 kip
Supported gross area Ag144 in²
Minimum interface steel0.72 in²
Provided interface steel1.24 in²

Original example

Worked solution

Default calculator ↗

Starting inputs

Support width
12 in
Support length
12 in
Factored compression Pu
260 kip

Calculated result

Design bearing φBn
318.24 kip
Supporting area A₂ used
144 in²
Confinement multiplier
1
Demand beyond concrete bearing
0 kip

With no side projection on the controlling edge, use the unconfined bearing expression.

Preset screening · Basic bearing · Within limits

How the check works

Code basis ↗
  1. Take A₁ as loaded width × length. At 1V:2H the uniform side projection is limited by 2 × depth and the nearest support edge. The resulting footprint bounds A₂.
  2. Use φBn = 0.65 × 0.85f′c A₁ × min(√(A₂/A₁), 2). Confinement requires support beyond all loaded edges. Report any Pu above φBn as force requiring a separately designed transfer path.
  3. For a cast-in-place column or pedestal to foundation, compare the provided interface steel with 0.005 times supported gross area. A₁ is the default when it represents the gross area of the supported member.