Worked example · ASCE/SEI 7-16 §§11.4–11.6, 12.8

High-S₁ steel tower

A tall frame has mapped S₁ above 0.6 g and an analytical period beyond the long-period transition. Compare the high-S₁ floor with the period cap.

Calculation sheet
Export

Inputs

Hazard and occupancy
g
g
Structure
ft
kip
Period and level schedule

A zero elevation uses uniform spacing. The top level is fixed at 100%. The worksheet apportions W using the relative weights.

Period parameters

Use the coefficient for hₙ in feet in either display mode.

Enter 0 to use Table 12.8-1.

s

Enter 0 to use Tₐ.

s
Level 1
%
Level 2
%
Level 3
%
Level 4
%
Level 5
%
Level 6
%
Level 7
%
Level 8
%
Level 9
%
Level 10
BASE SHEAR
2,242.5kip
RESPONSE Cₛ
0.0488
PERIOD T
7.2s
DESIGN CAT.
E
Seismic Design Category E review

Mapped S₁ is at least 0.75 g. Verify the permitted analysis procedure and system restrictions.

Story force elevationFₓ peak 582.47 kiphₙ 780 ftDesign response spectrumSₐ (g)T = 7.2 s1.18008.6 s5% referenceStrength period
Level-force vectors and the two-period design spectrum. The active point uses the strength period.

Calculation detail

Site coefficients Fₐ / Fᵥ
1.2 / 1.4
Mapped site response Sᴍₛ
1.608 g
Mapped site response Sᴍ₁
1.092 g
Short-period design Sᴅₛ
1.072 g
One-second design Sᴅ₁
0.728 g
Importance factor Iₑ
1
Approximate Tₐ
5.765 s
Upper period CᵤTₐ
8.072 s
Period cap on Cₛ
0.00878
General minimum Cₛ
0.04717
High-S₁ minimum Cₛ
0.04875
Governing Cₛ check
High S₁ minimum
Distribution exponent k
2
Story force schedule
LevelElevation (ft)Weight (kip)CᵥₓFₓ (kip)Vₓ (kip)
1784,6000.00265.82472,242.5
21564,6000.010423.29872,236.6753
32344,6000.023452.42212,213.3766
43124,6000.041693.19482,160.9545
53904,6000.0649145.61692,067.7597
64684,6000.0935209.68831,922.1429
75464,6000.1273285.40911,712.4545
86244,6000.1662372.77921,427.0455
97024,6000.2104471.79871,054.2662
107804,6000.2597582.4675582.4675

How the calculation works

Read this example

The mapped high-S₁ minimum can exceed the period-based cap. Check the E/F design category rule and whether ELF is permitted.

Preset result: BASE SHEAR 2,242.5 kip.

From mapped hazard to the design spectrum

Interpolate Fₐ and Fᵥ using the ASCE 7-16 Supplement 3 tables. Default Site Class D uses a minimum Fₐ of 1.2. Sᴍₛ = FₐSₛ and Sᴍ₁ = FᵥS₁. Multiply each by 2/3 for the design ordinates. The design category uses the more severe result of the two SDC tables and the high-S₁ rule. Class B values assume measured rock velocity.

Strength period and governing coefficient

Tₐ = Cₜhₙˣ. The entered model period is capped by CᵤTₐ for strength. Cₛ starts at Sᴅₛ/(R/Iₑ), uses the smaller applicable upper value from Eq. 12.8-3 or 12.8-4, and then applies both lower bounds in Eqs. 12.8-5 and 12.8-6.

Level forces and shears

V = CₛW. Each level receives a share proportional to wₓhₓᵏ. k rises linearly from 1 at 0.5 s to 2 at 2.5 s. A story shear is the sum of its level force and all level forces above.

Site-specific screening and Supplement 3

For Site Class D at S₁ ≥ 0.2 g the selected exception increases Sᴍ₁ by 50%. For Site Class E at Sₛ ≥ 1.0 g or S₁ ≥ 0.2 g the selected ELF exception uses Eq. 12.8-2 for all periods, subject to the Cₛ minimums. Confirm that the exception is applicable before selecting it.

Design scope

Verify ELF eligibility, approved hazard data, system coefficients and the adopted supplement before using these loads. Site-specific ground motion analysis requires separate hazard and geotechnical data.

Source references
  • ASCE/SEI 7-16 standardhttps://ascelibrary.org/doi/book/10.1061/9780784414248
  • ASCE 7-16 Supplement 3https://ascelibrary.org/doi/pdf/10.1061/9780784414248.sup3
  • ASCE Hazard Toolhttps://www.asce.org/publications-and-news/asce-hazard-tool/
  • FEMA P-1051 design exampleshttps://www.fema.gov/sites/default/files/2020-07/fema_nehrp-seismic-provisions-examples_p-1051_20160701.pdf

More seismic base shear examples