Worked example · ASCE/SEI 7-16 §§26.9–26.13, 27.3, 30.3

Low-roof entrance pavilion

A small enclosed entrance structure has both the wall evaluation point and the eave below 15 ft. This tests the low-height exposure clamp.

Calculation sheet
Export

Inputs

Wind and exposure
mph
ft
ft

Use eave height for roof slopes of 10° or less.

Building envelope
ft
ft
°
Wind factors, opening and C&C
Velocity and pressure factors
ft
ft²

0 retains the unreduced −1.3 coefficient.

Low-rise components and cladding
VELOCITY qz
20.365psf
ROOF qh
20.365psf
EXPOSURE Kz
0.849
ROOF MIN.
-19.245psf

Building pressure sectionWindwardLeewardGCₚᵢ ±0.18h 14 ftExposure with heightHeight zExposure C17.3 ft001.13Kz exposure factor15 ft floor
Wall pressure directions and the exposure profile. Arrow lengths reflect the active wind pressure cases.

Calculation detail

Ground elevation Kₑ
1
Roof exposure Kₕ
0.849
Positive internal qᵢ
20.365 psf
Internal coefficient |GCₚᵢ|
0.18
Leeward Cₚ
-0.417
Aspect L/B
1.417
Directional surface pressures
SurfaceCₚExternal (psf)+GCₚᵢ (psf)−GCₚᵢ (psf)
Windward wall0.813.848210.182517.514
Leeward wall-0.4167-7.2126-10.8783-3.5469
Sidewall-0.7-12.1172-15.7829-8.4515
Roof strip 1-0.9-15.5793-19.245-11.9136
Roof strip 1 / alt.-0.18-3.1159-6.78160.5499
Roof strip 2-0.9-15.5793-19.245-11.9136
Roof strip 2 / alt.-0.18-3.1159-6.78160.5499
Roof strip 3-0.5-8.6552-12.3209-4.9894
Roof strip 3 / alt.-0.18-3.1159-6.78160.5499
Roof strip 4-0.3-5.1931-8.8588-1.5274
Roof strip 4 / alt.-0.18-3.1159-6.78160.5499
Roof strip limits from windward edge
StripFrom (ft)To (ft)
Roof strip 107
Roof strip 2714
Roof strip 31428
Roof strip 42834

How the calculation works

Read this example

qz and qh are equal while both reference heights stay below 15 ft.

Preset result: VELOCITY qz 20.365 psf.

Velocity pressure changes with height

Kz = 2.01(z/zg)^(2/α) in the exposure layer. The evaluation height has a 15 ft floor and a ceiling at the gradient height. The worksheet evaluates the original mph/ft equation qz = 0.00256 Kz Kzt Kd Ke V². Ke = exp(−0.0000362 zₑ), with zₑ in feet.

Surface coefficients and pressure signs

The Chapter 27 directional procedure uses local qz at the windward wall and qh at the leeward and side walls and roof. Leeward wall Cₚ is interpolated using L/B. Roof strips follow distance downwind for low slope or parallel wind, and gable slopes use h/L and slope interpolation normal to the ridge.

Keep internal cases paired

Net pressure is external qGCₚ minus internal qᵢGCₚᵢ. Windward dominant opening height can set positive qᵢ for a partially enclosed building. Negative internal pressure uses qh. A positive surface result acts toward the face. Apply a consistent internal-pressure sign to the building for a load case.

Calculate low-rise C&C pressure for a selected zone

Choose the zone and both external GCₚ values from the applicable Chapter 30 figure for the roof geometry and effective wind area. Eq. 30.3-1 uses qh for both terms and includes the adverse internal sign for each direction. The reported design magnitude is at least 16 psf inward and outward. The external coefficient already includes gust effect.

Design scope

Directional MWFRS screening for rectangular flat or gable buildings. Check governing load cases and minimums separately. The optional C&C check uses the supplied low-rise zone coefficients. Chapter 28 envelope cases, open-roof net coefficients, torsional load cases and overhangs use distinct provisions.