How the calculation works
Read this example
The simplified amplification is unavailable when the calculated stability coefficient exceeds the maximum.
Preset result: STORY DRIFT 4.74 in.
Convert the analysis drift
Design story drift Δ = Cᴅδₓₑ/Iₑ. Divide by the story height in consistent units and compare against the specified screening row of Table 12.12-1. Most masonry shear walls use 0.007, and masonry cantilever shear walls use 0.010.
Evaluate stability before applying amplification
θ = PₓΔIₑ/(VₓhₛₓCᴅ) and θmax = min(0.5/(βCᴅ), 0.25). Above θmax, the story is potentially unstable. Within the maximum, θ greater than 0.10 requires explicit second-order analysis or the permitted 1/(1 − θ) amplification.
Check the qualifications for drift exceptions
The ≤4-story row assumes the relevant interior and exterior assemblies accommodate drift. The single-story exception also requires detailed drift accommodation. Building separation and the special requirement for certain moment frames in seismic categories D–F are separate checks.
Design scope
Use drifts and forces from the applicable seismic analysis in the same direction. Check building separation, moment-frame rules, and drift compatibility in addition to this worksheet.