ISO 3 lithography bay

A small lithography bay uses a full-ceiling unidirectional velocity model with metric FFU modules.

Inputs

Room geometry
m
m
m
Supply & ceiling
m/s
m³/h
Use the rated flow at the planned operating pressure.

Live results

Ceiling grid and particle curve

Ceiling grid and particle curveSUPPLY FLOW26,130m³/hAIR CHANGES540h⁻¹FFU COUNT22unitsCOVERAGE91.67%FFU ceiling gridDownflow supplyISO 3 · particles/m³110⁴10⁸0.10.20.30.515µmUniform ceiling fitFFU count22 neededGrid 24 units
Filled ceiling cells represent the share covered by FFUs. Hollow circles on the particle curve mark formula-only values.

The required FFU count fits the uniform grid before service clearances.

Supply flow
26,127.4 m³/h
Air changes
540 h⁻¹
FFU count
22 units
Coverage
91.6667 %

Room and airflow

Floor area
17.28 m²
Room volume
48.384 m³
Installed FFU capacity
26,400 m³/h
Capacity above target
272.64 m³/h
100:1 ideal recovery
0.511686 min

Ceiling layout

Installed FFU face area
15.84 m²
Uniform grid capacity
24 units

Particle concentrations (particles/m³)

ThresholdFormulaISO table limit
≥ 0.1 µm1,0001,000
≥ 0.2 µm236.5144237
≥ 0.3 µm101.7625102
≥ 0.5 µm35.1675735
≥ 1 µm8.317638Unassigned
≥ 5 µm0.2925111Unassigned

Counts are cumulative. Use the published classification value for each applicable class and particle size.

Worked calculation at the starting values

Compare the required 22 filters with the 24-module uniform-grid capacity before allowing for lights and service clearances.

  1. Room volume = 4.8 × 3.6 × 2.8 = 48.384 m³.
  2. Supply = 17.28 × 0.42 = 7.2576 m³/s.
  3. FFU count = round up (7.2576 ÷ 0.3333333) = 22 units.
Starting result snapshot
Supply flow
26,127.4 m³/h
Air changes
540 h⁻¹
FFU count
22 units
Coverage
91.6667 %

Equations and assumptions

Particle concentration

Cₙ = 10ᴺ × (0.1 ÷ D)²·⁰⁸

D is the threshold particle size in µm. Each value includes particles at or above D and is reported in particles/m³. Formula values are shown for all six sizes. Use the separate ISO 14644-1:2015 Table 1 column when a class/size limit is published.

Supply airflow

Q = A × H × ACH ÷ 3600 or Q = A × v

Use SI dimensions (m and m²), v in m/s and Q in m³/s. The unidirectional case assumes flow over the full floor plan. The selected ISO class sets particle criteria independently of the airflow target.

FFU count and ceiling fit

n = ceil(Q ÷ Q_FFU) · coverage = n × A_FFU ÷ A × 100%

Grid capacity uses the better of two uniform module orientations. Lights, sprinklers, service clearance and mixed-orientation layouts need a separate ceiling plan.

100:1 recovery

t₁₀₀ = 60 × ln(100) ÷ ACH

This minute estimate assumes perfect mixing, no continuing source and contaminant-free supply. Measure recovery when applicable under ISO 14644-3. For unidirectional flow it remains a mixed-air benchmark.