ISO 4 mask inspection

An inspection room uses an entered mixed-air target of 130 changes per hour.

Inputs

Room geometry
ft
ft
ft
Supply & ceiling
h⁻¹
CFM
Use the rated flow at the planned operating pressure.

Live results

Ceiling grid and particle curve

Ceiling grid and particle curveSUPPLY FLOW5,460CFMAIR CHANGES130h⁻¹FFU COUNT8unitsCOVERAGE22.86%FFU ceiling gridMixed-air supplyISO 4 · particles/m³110⁴10⁸0.10.20.30.515µmUniform ceiling fitFFU count8 neededGrid 35 units
Filled ceiling cells represent the share covered by FFUs. Hollow circles on the particle curve mark formula-only values.

The required FFU count fits the uniform grid before service clearances.

Supply flow
5,460 CFM
Air changes
130 h⁻¹
FFU count
8 units
Coverage
22.8571 %

Room and airflow

Floor area
280 ft²
Room volume
2,520 ft³
Installed FFU capacity
5,760 CFM
Capacity above target
300 CFM
100:1 ideal recovery
2.12546 min

Ceiling layout

Installed FFU face area
64 ft²
Uniform grid capacity
35 units

Particle concentrations (particles/m³)

ThresholdFormulaISO table limit
≥ 0.1 µm10,00010,000
≥ 0.2 µm2,365.1442,370
≥ 0.3 µm1,017.6251,020
≥ 0.5 µm351.6757352
≥ 1 µm83.1763883
≥ 5 µm2.925111Unassigned

Counts are cumulative. Use the published classification value for each applicable class and particle size.

Worked calculation at the starting values

Check the filter count after rounding up and compare the installed area with the floor plan.

  1. Room volume = 6.096 × 4.2672 × 2.7432 = 71.35845 m³.
  2. Supply = 71.35845 × 130 ÷ 3600 = 2.576833 m³/s.
  3. FFU count = round up (2.576833 ÷ 0.3398022) = 8 units.
Starting result snapshot
Supply flow
5,460 CFM
Air changes
130 h⁻¹
FFU count
8 units
Coverage
22.8571 %

Equations and assumptions

Particle concentration

Cₙ = 10ᴺ × (0.1 ÷ D)²·⁰⁸

D is the threshold particle size in µm. Each value includes particles at or above D and is reported in particles/m³. Formula values are shown for all six sizes. Use the separate ISO 14644-1:2015 Table 1 column when a class/size limit is published.

Supply airflow

Q = A × H × ACH ÷ 3600 or Q = A × v

Use SI dimensions (m and m²), v in m/s and Q in m³/s. The unidirectional case assumes flow over the full floor plan. The selected ISO class sets particle criteria independently of the airflow target.

FFU count and ceiling fit

n = ceil(Q ÷ Q_FFU) · coverage = n × A_FFU ÷ A × 100%

Grid capacity uses the better of two uniform module orientations. Lights, sprinklers, service clearance and mixed-orientation layouts need a separate ceiling plan.

100:1 recovery

t₁₀₀ = 60 × ln(100) ÷ ACH

This minute estimate assumes perfect mixing, no continuing source and contaminant-free supply. Measure recovery when applicable under ISO 14644-3. For unidirectional flow it remains a mixed-air benchmark.

References

More worked examples

Open calculator defaults