CleanroomVentLab · Calculation sheet · US customary
ISO 6 metrology room
Inputs
- Length
- 28 ft
- Width
- 15 ft
- Clear height
- 10 ft
- ISO class
- ISO Class 6
- Airflow basis
- Air changes per hour
- Target air changes
- 110 h⁻¹
- FFU nominal module
- 2 × 4 ft
- Rated flow per FFU
- 800 CFM
Results
- Supply flow
- 7,700 CFM
- Air changes
- 110 h⁻¹
- FFU count
- 10 units
- Coverage
- 19.0476 %
- Floor area
- 420 ft²
- Room volume
- 4,200 ft³
- Installed FFU capacity
- 8,000 CFM
- Capacity above target
- 300 CFM
- 100:1 ideal recovery
- 2.51191 min
- Installed FFU face area
- 80 ft²
- Uniform grid capacity
- 49 units
Particle concentrations (particles/m³)
| Threshold | Formula | ISO table limit |
|---|---|---|
| ≥ 0.1 µm | 1,000,000 | 1,000,000 |
| ≥ 0.2 µm | 236,514.4 | 237,000 |
| ≥ 0.3 µm | 101,762.5 | 102,000 |
| ≥ 0.5 µm | 35,167.57 | 35,200 |
| ≥ 1 µm | 8,317.638 | 8,320 |
| ≥ 5 µm | 292.5111 | 293 |
Counts are cumulative. Use the published classification value for each applicable class and particle size.
The required FFU count fits the uniform grid before service clearances.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.