ISO 6 metrology room

A metrology room runs at 110 air changes per hour and uses 2 × 4 ft FFUs.

Inputs

Room geometry
ft
ft
ft
Supply & ceiling
h⁻¹
CFM
Use the rated flow at the planned operating pressure.

Live results

Ceiling grid and particle curve

Ceiling grid and particle curveSUPPLY FLOW7,700CFMAIR CHANGES110h⁻¹FFU COUNT10unitsCOVERAGE19.05%FFU ceiling gridMixed-air supplyISO 6 · particles/m³110⁴10⁸0.10.20.30.515µmUniform ceiling fitFFU count10 neededGrid 49 units
Filled ceiling cells represent the share covered by FFUs. Hollow circles on the particle curve mark formula-only values.

The required FFU count fits the uniform grid before service clearances.

Supply flow
7,700 CFM
Air changes
110 h⁻¹
FFU count
10 units
Coverage
19.0476 %

Room and airflow

Floor area
420 ft²
Room volume
4,200 ft³
Installed FFU capacity
8,000 CFM
Capacity above target
300 CFM
100:1 ideal recovery
2.51191 min

Ceiling layout

Installed FFU face area
80 ft²
Uniform grid capacity
49 units

Particle concentrations (particles/m³)

ThresholdFormulaISO table limit
≥ 0.1 µm1,000,0001,000,000
≥ 0.2 µm236,514.4237,000
≥ 0.3 µm101,762.5102,000
≥ 0.5 µm35,167.5735,200
≥ 1 µm8,317.6388,320
≥ 5 µm292.5111293

Counts are cumulative. Use the published classification value for each applicable class and particle size.

Worked calculation at the starting values

Compare the installed flow margin caused by rounding the required unit count up to a whole module.

  1. Room volume = 8.5344 × 4.572 × 3.048 = 118.9308 m³.
  2. Supply = 118.9308 × 110 ÷ 3600 = 3.633995 m³/s.
  3. FFU count = round up (3.633995 ÷ 0.377558) = 10 units.
Starting result snapshot
Supply flow
7,700 CFM
Air changes
110 h⁻¹
FFU count
10 units
Coverage
19.0476 %

Equations and assumptions

Particle concentration

Cₙ = 10ᴺ × (0.1 ÷ D)²·⁰⁸

D is the threshold particle size in µm. Each value includes particles at or above D and is reported in particles/m³. Formula values are shown for all six sizes. Use the separate ISO 14644-1:2015 Table 1 column when a class/size limit is published.

Supply airflow

Q = A × H × ACH ÷ 3600 or Q = A × v

Use SI dimensions (m and m²), v in m/s and Q in m³/s. The unidirectional case assumes flow over the full floor plan. The selected ISO class sets particle criteria independently of the airflow target.

FFU count and ceiling fit

n = ceil(Q ÷ Q_FFU) · coverage = n × A_FFU ÷ A × 100%

Grid capacity uses the better of two uniform module orientations. Lights, sprinklers, service clearance and mixed-orientation layouts need a separate ceiling plan.

100:1 recovery

t₁₀₀ = 60 × ln(100) ÷ ACH

This minute estimate assumes perfect mixing, no continuing source and contaminant-free supply. Measure recovery when applicable under ISO 14644-3. For unidirectional flow it remains a mixed-air benchmark.

References

More worked examples

Open calculator defaults