CleanroomVentLab · Calculation sheet · US customary
ISO 7 tall process bay
Inputs
- Length
- 36 ft
- Width
- 20 ft
- Clear height
- 15 ft
- ISO class
- ISO Class 7
- Airflow basis
- Air changes per hour
- Target air changes
- 55 h⁻¹
- FFU nominal module
- 2 × 4 ft
- Rated flow per FFU
- 900 CFM
Results
- Supply flow
- 9,900 CFM
- Air changes
- 55 h⁻¹
- FFU count
- 11 units
- Coverage
- 12.2222 %
- Floor area
- 720 ft²
- Room volume
- 10,800 ft³
- Installed FFU capacity
- 9,900 CFM
- Capacity above target
- 0 CFM
- 100:1 ideal recovery
- 5.02382 min
- Installed FFU face area
- 88 ft²
- Uniform grid capacity
- 90 units
Particle concentrations (particles/m³)
| Threshold | Formula | ISO table limit |
|---|---|---|
| ≥ 0.1 µm | 10,000,000 | Unassigned |
| ≥ 0.2 µm | 2,365,144 | Unassigned |
| ≥ 0.3 µm | 1,017,625 | Unassigned |
| ≥ 0.5 µm | 351,675.7 | 352,000 |
| ≥ 1 µm | 83,176.38 | 83,200 |
| ≥ 5 µm | 2,925.111 | 2,930 |
Counts are cumulative. Use the published classification value for each applicable class and particle size.
The required FFU count fits the uniform grid before service clearances.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.