ISO 7 tall process bay

A tall process bay has the same ISO class as the compounding room and a larger conditioned air volume.

Inputs

Room geometry
ft
ft
ft
Supply & ceiling
h⁻¹
CFM
Use the rated flow at the planned operating pressure.

Live results

Ceiling grid and particle curve

Ceiling grid and particle curveSUPPLY FLOW9,900CFMAIR CHANGES55h⁻¹FFU COUNT11unitsCOVERAGE12.22%FFU ceiling gridMixed-air supplyISO 7 · particles/m³110⁴10⁸0.10.20.30.515µmUniform ceiling fitFFU count11 neededGrid 90 units
Filled ceiling cells represent the share covered by FFUs. Hollow circles on the particle curve mark formula-only values.

The required FFU count fits the uniform grid before service clearances.

Supply flow
9,900 CFM
Air changes
55 h⁻¹
FFU count
11 units
Coverage
12.2222 %

Room and airflow

Floor area
720 ft²
Room volume
10,800 ft³
Installed FFU capacity
9,900 CFM
Capacity above target
0 CFM
100:1 ideal recovery
5.02382 min

Ceiling layout

Installed FFU face area
88 ft²
Uniform grid capacity
90 units

Particle concentrations (particles/m³)

ThresholdFormulaISO table limit
≥ 0.1 µm10,000,000Unassigned
≥ 0.2 µm2,365,144Unassigned
≥ 0.3 µm1,017,625Unassigned
≥ 0.5 µm351,675.7352,000
≥ 1 µm83,176.3883,200
≥ 5 µm2,925.1112,930

Counts are cumulative. Use the published classification value for each applicable class and particle size.

Worked calculation at the starting values

Increasing clear height increases the supply required at a fixed ACH. The applicable particle limits stay the same.

  1. Room volume = 10.9728 × 6.096 × 4.572 = 305.8219 m³.
  2. Supply = 305.8219 × 55 ÷ 3600 = 4.67228 m³/s.
  3. FFU count = round up (4.67228 ÷ 0.4247527) = 11 units.
Starting result snapshot
Supply flow
9,900 CFM
Air changes
55 h⁻¹
FFU count
11 units
Coverage
12.2222 %

Equations and assumptions

Particle concentration

Cₙ = 10ᴺ × (0.1 ÷ D)²·⁰⁸

D is the threshold particle size in µm. Each value includes particles at or above D and is reported in particles/m³. Formula values are shown for all six sizes. Use the separate ISO 14644-1:2015 Table 1 column when a class/size limit is published.

Supply airflow

Q = A × H × ACH ÷ 3600 or Q = A × v

Use SI dimensions (m and m²), v in m/s and Q in m³/s. The unidirectional case assumes flow over the full floor plan. The selected ISO class sets particle criteria independently of the airflow target.

FFU count and ceiling fit

n = ceil(Q ÷ Q_FFU) · coverage = n × A_FFU ÷ A × 100%

Grid capacity uses the better of two uniform module orientations. Lights, sprinklers, service clearance and mixed-orientation layouts need a separate ceiling plan.

100:1 recovery

t₁₀₀ = 60 × ln(100) ÷ ACH

This minute estimate assumes perfect mixing, no continuing source and contaminant-free supply. Measure recovery when applicable under ISO 14644-3. For unidirectional flow it remains a mixed-air benchmark.

References

More worked examples

Open calculator defaults