ISO 8 material airlock

A material airlock uses a 35-ACH recirculation target and metric filter modules.

Inputs

Room geometry
m
m
m
Supply & ceiling
h⁻¹
m³/h
Use the rated flow at the planned operating pressure.

Live results

Ceiling grid and particle curve

Ceiling grid and particle curveSUPPLY FLOW917.3m³/hAIR CHANGES35h⁻¹FFU COUNT2unitsCOVERAGE14.29%FFU ceiling gridMixed-air supplyISO 8 · particles/m³110⁴10⁸0.10.20.30.515µmUniform ceiling fitFFU count2 neededGrid 14 units
Filled ceiling cells represent the share covered by FFUs. Hollow circles on the particle curve mark formula-only values.

The required FFU count fits the uniform grid before service clearances.

Supply flow
917.28 m³/h
Air changes
35 h⁻¹
FFU count
2 units
Coverage
14.2857 %

Room and airflow

Floor area
10.08 m²
Room volume
26.208 m³
Installed FFU capacity
1,700 m³/h
Capacity above target
782.72 m³/h
100:1 ideal recovery
7.89458 min

Ceiling layout

Installed FFU face area
1.44 m²
Uniform grid capacity
14 units

Particle concentrations (particles/m³)

ThresholdFormulaISO table limit
≥ 0.1 µm100,000,000Unassigned
≥ 0.2 µm23,651,440Unassigned
≥ 0.3 µm10,176,250Unassigned
≥ 0.5 µm3,516,7573,520,000
≥ 1 µm831,763.8832,000
≥ 5 µm29,251.1129,300

Counts are cumulative. Use the published classification value for each applicable class and particle size.

Worked calculation at the starting values

Verify the small room footprint against the uniform-grid fit and leave suitable space for ceiling services.

  1. Room volume = 4.2 × 2.4 × 2.6 = 26.208 m³.
  2. Supply = 26.208 × 35 ÷ 3600 = 0.2548 m³/s.
  3. FFU count = round up (0.2548 ÷ 0.2361111) = 2 units.
Starting result snapshot
Supply flow
917.28 m³/h
Air changes
35 h⁻¹
FFU count
2 units
Coverage
14.2857 %

Equations and assumptions

Particle concentration

Cₙ = 10ᴺ × (0.1 ÷ D)²·⁰⁸

D is the threshold particle size in µm. Each value includes particles at or above D and is reported in particles/m³. Formula values are shown for all six sizes. Use the separate ISO 14644-1:2015 Table 1 column when a class/size limit is published.

Supply airflow

Q = A × H × ACH ÷ 3600 or Q = A × v

Use SI dimensions (m and m²), v in m/s and Q in m³/s. The unidirectional case assumes flow over the full floor plan. The selected ISO class sets particle criteria independently of the airflow target.

FFU count and ceiling fit

n = ceil(Q ÷ Q_FFU) · coverage = n × A_FFU ÷ A × 100%

Grid capacity uses the better of two uniform module orientations. Lights, sprinklers, service clearance and mixed-orientation layouts need a separate ceiling plan.

100:1 recovery

t₁₀₀ = 60 × ln(100) ÷ ACH

This minute estimate assumes perfect mixing, no continuing source and contaminant-free supply. Measure recovery when applicable under ISO 14644-3. For unidirectional flow it remains a mixed-air benchmark.

References

More worked examples

Open calculator defaults