Cleanroom pressure cascade

Estimate door-crack leakage and the supply-minus-exhaust offset across a three-zone pressure ladder.

Inputs

Pressure setpoints
in.wg
in.wg
in.wg
in.wg
A–B leakage paths
ft
in
in²
B–C leakage paths
ft
in
in²
Air properties
0.60–0.65 is a common sharp-edge starting range.
lb/ft³

Live results

Three-zone pressure ladder

Three-zone pressure ladderA–B STEP+0.06022in.wgB–C STEP+0.06022in.wgZONE A OFFSET+85.39CFMZONE C OFFSET-82.11CFMClosed-door pressure and room offsetsZone A+0.1204 in.wg+85.39 CFMZone B+0.06022 in.wg-3.284 CFMZone C0 in.wg-82.11 CFMLowest aligned pressure stepPressure+0.06022 in.wgMin 0.06022 in.wg
Arrows follow the calculated pressure gradient. Positive offsets call for more supply and negative offsets call for more exhaust.

Both pressure steps meet the entered magnitude and direction.

A–B step
+0.0602195 in.wg
B–C step
+0.0602195 in.wg
Zone A offset
+85.3909 CFM
Zone C offset
-82.1066 CFM

Transfer at each barrier

A → B transfer
+85.3909 CFM
B → C transfer
+82.1066 CFM
A–B equivalent leakage
20.15 in²
B–C equivalent leakage
19.375 in²

Room offsets and ladder

Zone A supply minus exhaust
+85.3909 CFM
Zone B supply minus exhaust
-3.28426 CFM
Zone C supply minus exhaust
-82.1066 CFM
Weakest aligned step
+0.0602195 in.wg
Required step
0.0602195 in.wg

Equations and assumptions

Door-crack and other paths

A = perimeter × gap + A_other

Include only the portion of perimeter with a leak path. Enter wall, pass-through and fitting leakage as equivalent area at the same discharge coefficient.

Signed transfer flow

Qᵢⱼ = sgn(Pᵢ − Pⱼ) × C_d × A × √(2 × |Pᵢ − Pⱼ| ÷ ρ)

Use Pa, m² and kg/m³ for Q in m³/s. All three pressures share the same reference. The differential across each closed barrier determines both rate and direction.

Supply minus exhaust

A: Q_AB · B: Q_BC − Q_AB · C: −Q_BC

These are the room offsets attributable to the two modeled door links. Add other envelope paths and use a balanced airflow network for the full system. Open doors, transients and alarm tolerances require testing.

Ladder check

Minimum aligned step = min(s × ΔP_AB, s × ΔP_BC)

The sign s is +1 for an A-to-C cascade and −1 for containment toward A. The FDA closed-door aseptic guidance gives 10–15 Pa as a typical example between different clean classifications. Use the project pressure specification.