Negative powder suite

A powder handling room is Zone A, with successively higher pressures in the airlock and corridor.

Inputs

Pressure setpoints
Pa
Pa
Pa
Pa
A–B leakage paths
m
mm
mm²
B–C leakage paths
m
mm
mm²
Air properties
0.60–0.65 is a common sharp-edge starting range.
kg/m³

Live results

Three-zone pressure ladder

Three-zone pressure ladderA–B STEP-15PaB–C STEP-15PaZONE A OFFSET-111.6m³/hZONE C OFFSET+139.5m³/hClosed-door pressure and room offsetsZone A-30 Pa-111.6 m³/hZone B-15 Pa-27.9 m³/hZone C0 Pa+139.5 m³/hLowest aligned pressure stepPressure+15 PaMin 12 Pa
Arrows follow the calculated pressure gradient. Positive offsets call for more supply and negative offsets call for more exhaust.

Both pressure steps meet the entered magnitude and direction.

A–B step
-15 Pa
B–C step
-15 Pa
Zone A offset
-111.6 m³/h
Zone C offset
+139.5 m³/h

Transfer at each barrier

A → B transfer
-111.6 m³/h
B → C transfer
-139.5 m³/h
A–B equivalent leakage
10,000 mm²
B–C equivalent leakage
12,500 mm²

Room offsets and ladder

Zone A supply minus exhaust
-111.6 m³/h
Zone B supply minus exhaust
-27.9 m³/h
Zone C supply minus exhaust
+139.5 m³/h
Weakest aligned step
+15 Pa
Required step
12 Pa

Worked calculation at the starting values

With the intended containment direction selected, negative A–B transfer gives Zone A a negative supply-minus-exhaust offset.

  1. A–B equivalent leak area = 6 × 0.0015 + 0.001 = 0.01 m².
  2. A–B transfer magnitude = 0.62 × 0.01 × √(2 × 15 ÷ 1.2) = 0.031 m³/s.
  3. Zone B offset = -0.03875 − (-0.031) = -0.00775 m³/s.
Starting result snapshot
A–B step
-15 Pa
B–C step
-15 Pa
Zone A offset
-111.6 m³/h
Zone C offset
+139.5 m³/h

Equations and assumptions

Door-crack and other paths

A = perimeter × gap + A_other

Include only the portion of perimeter with a leak path. Enter wall, pass-through and fitting leakage as equivalent area at the same discharge coefficient.

Signed transfer flow

Qᵢⱼ = sgn(Pᵢ − Pⱼ) × C_d × A × √(2 × |Pᵢ − Pⱼ| ÷ ρ)

Use Pa, m² and kg/m³ for Q in m³/s. All three pressures share the same reference. The differential across each closed barrier determines both rate and direction.

Supply minus exhaust

A: Q_AB · B: Q_BC − Q_AB · C: −Q_BC

These are the room offsets attributable to the two modeled door links. Add other envelope paths and use a balanced airflow network for the full system. Open doors, transients and alarm tolerances require testing.

Ladder check

Minimum aligned step = min(s × ΔP_AB, s × ΔP_BC)

The sign s is +1 for an A-to-C cascade and −1 for containment toward A. The FDA closed-door aseptic guidance gives 10–15 Pa as a typical example between different clean classifications. Use the project pressure specification.

References