Tight interlocked doors

Both closed doors have small leakage gaps and different extra seal leakage allowances.

Inputs

Pressure setpoints
in.wg
in.wg
in.wg
in.wg
A–B leakage paths
ft
in
in²
B–C leakage paths
ft
in
in²
Air properties
0.60–0.65 is a common sharp-edge starting range.
lb/ft³

Live results

Three-zone pressure ladder

Three-zone pressure ladderA–B STEP+0.06022in.wgB–C STEP+0.06022in.wgZONE A OFFSET+13.98CFMZONE C OFFSET-17CFMClosed-door pressure and room offsetsZone A+0.1204 in.wg+13.98 CFMZone B+0.06022 in.wg+3.019 CFMZone C0 in.wg-17 CFMLowest aligned pressure stepPressure+0.06022 in.wgMin 0.06022 in.wg
Arrows follow the calculated pressure gradient. Positive offsets call for more supply and negative offsets call for more exhaust.

Both pressure steps meet the entered magnitude and direction.

A–B step
+0.0602195 in.wg
B–C step
+0.0602195 in.wg
Zone A offset
+13.9846 CFM
Zone C offset
-17.004 CFM

Transfer at each barrier

A → B transfer
+13.9846 CFM
B → C transfer
+17.004 CFM
A–B equivalent leakage
3.41001 in²
B–C equivalent leakage
4.14626 in²

Room offsets and ladder

Zone A supply minus exhaust
+13.9846 CFM
Zone B supply minus exhaust
+3.0194 CFM
Zone C supply minus exhaust
-17.004 CFM
Weakest aligned step
+0.0602195 in.wg
Required step
0.0602195 in.wg

Worked calculation at the starting values

At the same pressure differential, the smaller gaps reduce the modeled transfer and offset demand.

  1. A–B equivalent leak area = 6 × 0.00035 + 0.0001 = 0.0022 m².
  2. A–B transfer magnitude = 0.6 × 0.0022 × √(2 × 15 ÷ 1.2) = 0.0066 m³/s.
  3. Zone B offset = 0.008025 − (0.0066) = 0.001425 m³/s.
Starting result snapshot
A–B step
+0.0602195 in.wg
B–C step
+0.0602195 in.wg
Zone A offset
+13.9846 CFM
Zone C offset
-17.004 CFM

Equations and assumptions

Door-crack and other paths

A = perimeter × gap + A_other

Include only the portion of perimeter with a leak path. Enter wall, pass-through and fitting leakage as equivalent area at the same discharge coefficient.

Signed transfer flow

Qᵢⱼ = sgn(Pᵢ − Pⱼ) × C_d × A × √(2 × |Pᵢ − Pⱼ| ÷ ρ)

Use Pa, m² and kg/m³ for Q in m³/s. All three pressures share the same reference. The differential across each closed barrier determines both rate and direction.

Supply minus exhaust

A: Q_AB · B: Q_BC − Q_AB · C: −Q_BC

These are the room offsets attributable to the two modeled door links. Add other envelope paths and use a balanced airflow network for the full system. Open doors, transients and alarm tolerances require testing.

Ladder check

Minimum aligned step = min(s × ΔP_AB, s × ΔP_BC)

The sign s is +1 for an A-to-C cascade and −1 for containment toward A. The FDA closed-door aseptic guidance gives 10–15 Pa as a typical example between different clean classifications. Use the project pressure specification.

References

More worked examples

Open calculator defaults