Weak secondary step

The upstream link has a larger differential than the downstream link in an otherwise positive cascade.

Inputs

Pressure setpoints
Pa
Pa
Pa
Pa
A–B leakage paths
m
mm
mm²
B–C leakage paths
m
mm
mm²
Air properties
0.60–0.65 is a common sharp-edge starting range.
kg/m³

Live results

Three-zone pressure ladder

Three-zone pressure ladderA–B STEP+19PaB–C STEP+6PaZONE A OFFSET+166.8m³/hZONE C OFFSET-90.13m³/hClosed-door pressure and room offsetsZone A+25 Pa+166.8 m³/hZone B+6 Pa-76.67 m³/hZone C0 Pa-90.13 m³/hLowest aligned pressure stepPressure+6 PaMin 10 Pa
Arrows follow the calculated pressure gradient. Positive offsets call for more supply and negative offsets call for more exhaust.

At least one step is below the entered minimum.

A–B step
+19 Pa
B–C step
+6 Pa
Zone A offset
+166.794 m³/h
Zone C offset
-90.1251 m³/h

Transfer at each barrier

A → B transfer
+166.794 m³/h
B → C transfer
+90.1251 m³/h
A–B equivalent leakage
13,000 mm²
B–C equivalent leakage
12,500 mm²

Room offsets and ladder

Zone A supply minus exhaust
+166.794 m³/h
Zone B supply minus exhaust
-76.6689 m³/h
Zone C supply minus exhaust
-90.1251 m³/h
Weakest aligned step
+6 Pa
Required step
10 Pa

Worked calculation at the starting values

Both arrows can point the right way while the weaker step is below the specified minimum.

  1. A–B equivalent leak area = 6 × 0.002 + 0.001 = 0.013 m².
  2. A–B transfer magnitude = 0.62 × 0.013 × √(2 × 19 ÷ 1.15) = 0.04633167 m³/s.
  3. Zone B offset = 0.02503476 − (0.04633167) = -0.02129691 m³/s.
Starting result snapshot
A–B step
+19 Pa
B–C step
+6 Pa
Zone A offset
+166.794 m³/h
Zone C offset
-90.1251 m³/h

Equations and assumptions

Door-crack and other paths

A = perimeter × gap + A_other

Include only the portion of perimeter with a leak path. Enter wall, pass-through and fitting leakage as equivalent area at the same discharge coefficient.

Signed transfer flow

Qᵢⱼ = sgn(Pᵢ − Pⱼ) × C_d × A × √(2 × |Pᵢ − Pⱼ| ÷ ρ)

Use Pa, m² and kg/m³ for Q in m³/s. All three pressures share the same reference. The differential across each closed barrier determines both rate and direction.

Supply minus exhaust

A: Q_AB · B: Q_BC − Q_AB · C: −Q_BC

These are the room offsets attributable to the two modeled door links. Add other envelope paths and use a balanced airflow network for the full system. Open doors, transients and alarm tolerances require testing.

Ladder check

Minimum aligned step = min(s × ΔP_AB, s × ΔP_BC)

The sign s is +1 for an A-to-C cascade and −1 for containment toward A. The FDA closed-door aseptic guidance gives 10–15 Pa as a typical example between different clean classifications. Use the project pressure specification.

References