DallaValle approximation with k = 1 for plain hoods and k = 0.75 for flanged hoods. Use ft, ft² and FPM for CFM, or m, m² and m/s for m³/s. The result is sensitive to the square of X.
Long slot
Q = V_c × max(A, k × 3.7 × L × X)
L is slot length. The line-sink relation suits a long, narrow opening. The model uses face area as a lower bound at very short distances. Compare A/L to the capture distance and use a slot-specific design for nonuniform slots.
Face and duct velocity
V_face = Q ÷ A · V_duct = Q ÷ (π × D² ÷ 4)
The target is measured at the source. The face and duct values answer different questions. Presets between 50 and 2,000 FPM are starting points for different source energies and crossdrafts.
Entry and static suction
VP = (FPM ÷ 4005)² · |SPₕ| = (1 + Fₕ) × VP
VP is in in.wg at standard air density. Irrecoverable entry loss equals Fₕ × VP. Static suction is shown as a magnitude. Auto Fₕ uses example coefficients 0.93 for plain and 0.49 for flanged openings.
CleanroomVentLab · Calculation sheet · US customary
Metal grinding pickup
Inputs
Opening type
Freestanding face
Hood edge
Flanged opening
Face area
1.4 ft²
Capture distance
0.32 ft
Target capture velocity
2,000 FPM
Round duct diameter
12 in
Entry loss factor Fₕ
Automatic
Results
Exhaust flow
3,636 CFM
Source speed
2,000 FPM
Face speed
2,597.14 FPM
Static draw
1.9909 in.wg
Duct velocity
4,629.5 FPM
Duct velocity pressure
1.33617 in.wg
Entry loss coefficient
0.49
Irrecoverable entry loss
0.654725 in.wg
Hood static suction magnitude
1.9909 in.wg
Verify capture at the release point under operating crossdrafts.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.