Metal grinding pickup

A close-coupled flanged hood uses the high-energy grinding preset to screen exhaust.

Inputs

Hood geometry
ft²
ft
Velocity & duct
FPM
in
Use −1 for the default by hood edge.

Live results

Capture contours and exhaust path

Capture contours and exhaust pathEXHAUST FLOW3,636CFMSOURCE SPEED2,000FPMFACE SPEED2,597FPMSTATIC DRAW1.991in.wgSource and capture fieldExhaust ductX = 0.32 ftSource distance screenDistance X0.32 ftGuide 1.5 × Ø
The source marker moves with capture distance. Cerulean paths show air entering the hood and continuing into the exhaust duct.

Verify capture at the release point under operating crossdrafts.

Exhaust flow
3,636 CFM
Source speed
2,000 FPM
Face speed
2,597.14 FPM
Static draw
1.9909 in.wg

Duct and entrance

Duct velocity
4,629.5 FPM
Duct velocity pressure
1.33617 in.wg
Entry loss coefficient
0.49
Irrecoverable entry loss
0.654725 in.wg
Hood static suction magnitude
1.9909 in.wg

Worked calculation at the starting values

Verify wheel direction and guard geometry. The empirical capture equation uses the entered distance to the release point.

  1. Reach area = 10 × 0.097536² + 0.1300643 in m².
  2. Required flow = 1.716001 m³/s at 10.16 m/s capture velocity with the entered hood geometry.
  3. Static suction = (1 + 0.49) × 332.8261 = 495.9108 Pa.
Starting result snapshot
Exhaust flow
3,636 CFM
Source speed
2,000 FPM
Face speed
2,597.14 FPM
Static draw
1.9909 in.wg

Equations and assumptions

Freestanding face

Q = k × V_c × (10 × X² + A)

DallaValle approximation with k = 1 for plain hoods and k = 0.75 for flanged hoods. Use ft, ft² and FPM for CFM, or m, m² and m/s for m³/s. The result is sensitive to the square of X.

Long slot

Q = V_c × max(A, k × 3.7 × L × X)

L is slot length. The line-sink relation suits a long, narrow opening. The model uses face area as a lower bound at very short distances. Compare A/L to the capture distance and use a slot-specific design for nonuniform slots.

Face and duct velocity

V_face = Q ÷ A · V_duct = Q ÷ (π × D² ÷ 4)

The target is measured at the source. The face and duct values answer different questions. Presets between 50 and 2,000 FPM are starting points for different source energies and crossdrafts.

Entry and static suction

VP = (FPM ÷ 4005)² · |SPₕ| = (1 + Fₕ) × VP

VP is in in.wg at standard air density. Irrecoverable entry loss equals Fₕ × VP. Static suction is shown as a magnitude. Auto Fₕ uses example coefficients 0.93 for plain and 0.49 for flanged openings.