DallaValle approximation with k = 1 for plain hoods and k = 0.75 for flanged hoods. Use ft, ft² and FPM for CFM, or m, m² and m/s for m³/s. The result is sensitive to the square of X.
Long slot
Q = V_c × max(A, k × 3.7 × L × X)
L is slot length. The line-sink relation suits a long, narrow opening. The model uses face area as a lower bound at very short distances. Compare A/L to the capture distance and use a slot-specific design for nonuniform slots.
Face and duct velocity
V_face = Q ÷ A · V_duct = Q ÷ (π × D² ÷ 4)
The target is measured at the source. The face and duct values answer different questions. Presets between 50 and 2,000 FPM are starting points for different source energies and crossdrafts.
Entry and static suction
VP = (FPM ÷ 4005)² · |SPₕ| = (1 + Fₕ) × VP
VP is in in.wg at standard air density. Irrecoverable entry loss equals Fₕ × VP. Static suction is shown as a magnitude. Auto Fₕ uses example coefficients 0.93 for plain and 0.49 for flanged openings.
CleanroomVentLab · Calculation sheet · US customary
Plain slot coating station
Inputs
Opening type
Long slot
Hood edge
Plain opening
Face area
0.8 ft²
Capture distance
0.65 ft
Slot length
5 ft
Target capture velocity
120 FPM
Round duct diameter
8 in
Entry loss factor Fₕ
1.1
Results
Exhaust flow
1,443 CFM
Source speed
120 FPM
Face speed
1,803.75 FPM
Static draw
2.23734 in.wg
Duct velocity
4,133.89 FPM
Duct velocity pressure
1.0654 in.wg
Entry loss coefficient
1.1
Irrecoverable entry loss
1.17194 in.wg
Hood static suction magnitude
2.23734 in.wg
Estimated slot width
1.92 in
Length-to-width ratio
31.25 ×
Verify capture at the release point under operating crossdrafts.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.