Tank edge slot

A narrow, flanged slot along a tank edge is represented by its face area and long dimension.

Inputs

Hood geometry
m²
m
m
Velocity & duct
m/s
mm
Use −1 for the default by hood edge.

Live results

Capture contours and exhaust path

Capture contours and exhaust pathEXHAUST FLOW1,516m³/hSOURCE SPEED0.55m/sFACE SPEED7.021m/sSTATIC DRAW393.6PaSource and capture fieldExhaust ductX = 0.23 mSlot line-sink regionArea terms12.77× face areaFloor 1×
The source marker moves with capture distance. Cerulean paths show air entering the hood and continuing into the exhaust duct.

Verify capture at the release point under operating crossdrafts.

Exhaust flow
1,516.48 m³/h
Source speed
0.55 m/s
Face speed
7.02075 m/s
Static draw
393.566 Pa

Duct and entrance

Duct velocity
20.951 m/s
Duct velocity pressure
264.139 Pa
Entry loss coefficient
0.49
Irrecoverable entry loss
129.428 Pa
Hood static suction magnitude
393.566 Pa

Slot geometry

Estimated slot width
50 mm
Length-to-width ratio
24 ×

Worked calculation at the starting values

The long-slot estimate scales approximately with distance and length. Inspect the calculated slot width and aspect ratio.

  1. Slot reach term = 3.7 × 1.2 × 0.23 in m².
  2. Required flow = 0.421245 m³/s at 0.55 m/s capture velocity with the entered hood geometry.
  3. Static suction = (1 + 0.49) × 264.1385 = 393.5664 Pa.
Starting result snapshot
Exhaust flow
1,516.48 m³/h
Source speed
0.55 m/s
Face speed
7.02075 m/s
Static draw
393.566 Pa

Equations and assumptions

Freestanding face

Q = k × V_c × (10 × X² + A)

DallaValle approximation with k = 1 for plain hoods and k = 0.75 for flanged hoods. Use ft, ft² and FPM for CFM, or m, m² and m/s for m³/s. The result is sensitive to the square of X.

Long slot

Q = V_c × max(A, k × 3.7 × L × X)

L is slot length. The line-sink relation suits a long, narrow opening. The model uses face area as a lower bound at very short distances. Compare A/L to the capture distance and use a slot-specific design for nonuniform slots.

Face and duct velocity

V_face = Q ÷ A · V_duct = Q ÷ (π × D² ÷ 4)

The target is measured at the source. The face and duct values answer different questions. Presets between 50 and 2,000 FPM are starting points for different source energies and crossdrafts.

Entry and static suction

VP = (FPM ÷ 4005)² · |SPₕ| = (1 + Fₕ) × VP

VP is in in.wg at standard air density. Irrecoverable entry loss equals Fₕ × VP. Static suction is shown as a magnitude. Auto Fₕ uses example coefficients 0.93 for plain and 0.49 for flanged openings.

References