The sensible terms use temperature changes above and below the freezing point. A batch starting below freezing uses only the last term. A batch stopping at the freezing point ends before the latent stage in this model.
Estimated core pull-down
t = Etotal / (3,600 × Qrated × effectiveness)
For E in kJ and Q in kW the answer is hours. Pack geometry, access to air, and surface/core gradients are folded into one estimated effectiveness. Validate core temperatures with probes under the intended loading.
Why does the curve have a plateau during freezing?
At the nominal freezing point, the unit removes latent heat while the idealized core temperature stays level. Food typically freezes across a temperature range, so a measured trace may have a sloped transition.
Can I use rated room cooling capacity for a dense batch?
Use the output at the actual suction and condensing conditions. Derate the share reaching the batch and confirm with probes at the slowest-cooling location.
ColdChainLab · Engineering calculation
Blast Chiller & Product Freezing Time Calculator
Metric SI · https://calcsheetlab.com/coldchainlab/blast-chiller-freezing-time/
Inputs
Batch mass
320 kg
Initial core temperature
12 °C
Target core temperature
-18 °C
Product freeze point
-1.7 °C
Specific heat above freezing
3.65 kJ/(kg·K)
Specific heat below freezing
1.8 kJ/(kg·K)
Latent heat of fusion
252 kJ/kg
Rated refrigeration capacity
26 kW
Effective batch capacity
68 %
Results
Pull-down time
1.67h
Heat removed
106,030kJ
Effective rate
17.68kW
Freeze time
1.27h
Sensible heat above freezing
16,002kJ
Heat of fusion
80,640kJ
Sensible heat below freezing
9,389kJ
Heat per unit mass
331.35kJ/kg
Time above freezing
0.25h
Time below freezing
0.15h
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.