The sensible terms use temperature changes above and below the freezing point. A batch starting below freezing uses only the last term. A batch stopping at the freezing point ends before the latent stage in this model.
Estimated core pull-down
t = Etotal / (3,600 × Qrated × effectiveness)
For E in kJ and Q in kW the answer is hours. Pack geometry, access to air, and surface/core gradients are folded into one estimated effectiveness. Validate core temperatures with probes under the intended loading.
What should I check in the freezing a batch of berries example?
Inspect how much time is assigned to fusion. Tray packing and airflow can change effective capacity at the same equipment rating.
ColdChainLab · Engineering calculation
Freezing a batch of berries
Metric SI · https://calcsheetlab.com/coldchainlab/blast-chiller-freezing-time/berry-batch-freezing/
Inputs
Batch mass
420 kg
Initial core temperature
5 °C
Target core temperature
-17 °C
Product freeze point
-0.9 °C
Specific heat above freezing
3.8 kJ/(kg·K)
Specific heat below freezing
1.88 kJ/(kg·K)
Latent heat of fusion
280 kJ/kg
Rated refrigeration capacity
36 kW
Effective batch capacity
67 %
Results
Pull-down time
1.61h
Heat removed
139,729kJ
Effective rate
24.12kW
Freeze time
1.35h
Sensible heat above freezing
9,416kJ
Heat of fusion
117,600kJ
Sensible heat below freezing
12,713kJ
Heat per unit mass
332.69kJ/kg
Time above freezing
0.11h
Time below freezing
0.15h
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.