Product cooling

Blast Chiller & Product Freezing Time Calculator

Estimate the heat removal and pull-down time for a batch from initial to target core temperature, including its freezing plateau.

Pull-down time
1.67h
Heat removed
106,030kJ
Effective rate
17.68kW
Freeze time
1.27h
Edit inputs

Inputs

Edit any value to recalculate.

Batch & temperatures
kg
°C
°C
°C
Product properties
kJ/(kg·K)
kJ/(kg·K)
kJ/kg
Equipment

Enter refrigeration output at the actual operating condition. The percentage is the share available to remove product heat.

kW
%

Core temperature pull-down

Core temperature pull-downA constant effective capacity turns each sensible or latent heat term into the length of its stage.Core temperature / °CElapsed time / h00.40.91.31.7-21.6-9.23.215.6Above freezePhase changeBelow freeze

A constant effective capacity turns each sensible or latent heat term into the length of its stage.

Calculation breakdown

Sensible heat above freezing
16,002kJ
Heat of fusion
80,640kJ
Sensible heat below freezing
9,389kJ
Heat per unit mass
331.35kJ/kg
Time above freezing
0.25h
Time below freezing
0.15h

Worked examples

Open a case with its assumptions loaded, then edit the inputs.

Formulas and assumptions

Three-stage batch enthalpy

Etotal = m × c₊ΔT₊ + m × Lf + m × c₋ΔT₋

The sensible terms use temperature changes above and below the freezing point. A batch starting below freezing uses only the last term. A batch stopping at the freezing point ends before the latent stage in this model.

Estimated core pull-down

t = Etotal / (3,600 × Qrated × effectiveness)

For E in kJ and Q in kW the answer is hours. Pack geometry, access to air, and surface/core gradients are folded into one estimated effectiveness. Validate core temperatures with probes under the intended loading.

References

Questions and answers

Why does the curve have a plateau during freezing?

At the nominal freezing point, the unit removes latent heat while the idealized core temperature stays level. Food typically freezes across a temperature range, so a measured trace may have a sloped transition.

Can I use rated room cooling capacity for a dense batch?

Use the output at the actual suction and condensing conditions. Derate the share reaching the batch and confirm with probes at the slowest-cooling location.