The area factor covers circulation and unavailable floor area. The clear height check uses the overhead clearance and rack level pitch. Verify rows, egress, fire protection, and structure separately.
Apply peak and off-peak load percentages over their daily hours. Heater kWh is power × cycles × cycle hours × days. Convert retained room heat into compressor recovery electricity at the entered kW/TR.
Peak adds the compressor, active heater, and auxiliaries if they run together. With staging, the compressor draw must cover its daily energy and defrost recovery during the heater-off hours. If that requires more than rated draw, the staged peak is unavailable. The tariff estimate covers energy charges.
What should I check in the seasonal frozen storage facility example?
Enter the actual number of days the modeled loads operate. Add any separate off-season holding energy to the annual budget.
ColdChainLab · Engineering calculation
Seasonal frozen storage facility
Metric SI · https://calcsheetlab.com/coldchainlab/cold-storage-warehouse-energy/seasonal-frozen-storage/
Inputs
Interior length
28 m
Interior width
21 m
Interior height
6.5 m
Overhead clearance
0.7 m
Rack level pitch
1.9 m
Planned rack levels
3
Aisles & non-rack area
47 %
Position length
1.26 m
Position width
1.12 m
Reference refrigeration load
135 kW
Compressor input per ton
1.28 kW/TR
Peak profile length
6 h/day
Peak load fraction
90 %
Off-peak load fraction
36 %
Continuous auxiliary power
6 kW
Operating days per year
245 days
Active defrost heater power
36 kW
Defrost cycles
2 cycles/day
Time per defrost cycle
24 min
Defrost heat left in room
70 %
Compressor and heater timing
Loads may overlap
Billing currency
EUR · Euro
Electricity rate
0.18 EUR/kWh
Results
Rack positions
660
Annual energy
187,146kWh/yr
Annual cost
33,686EUR/yr
Peak draw
86.2kW
Energy cost per position per month
4.25EUR/position/mo
Usable rack levels
3
Positions per rack level
220
Net rack floor area
311.6m²
Equivalent full-load hours per day
11.88h/day
Base compressor electricity
143,012kWh/yr
Defrost heater electricity
7,056kWh/yr
Defrost heat returned to room
4,939kWhₜₕ/yr
Defrost recovery electricity
1,798kWh/yr
Auxiliary electricity
35,280kWh/yr
Defrost heater on-time
0.8h/day
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.