Input and output at one operating point
COP = Qevap / Wcomp • EER = 3.41214 × COP
These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.
Equipment selection
Compare compressor COP and EER with the Carnot limit, calculate condenser total heat rejection, and estimate air or water flow.
Edit any value to recalculate.
Heat absorbed at the evaporator and compressor electrical work combine at the condenser.
Open a case with its assumptions loaded, then edit the inputs.
A walk-in cooler has a measured compressor input and enough airflow to evaluate a candidate condenser temperature rise.
A refrigeration plant rejects heat to a water loop with a specified supply-to-return rise.
A freezer load drives a low evaporating saturation temperature relative to the condenser.
A medium-temperature circuit runs with a lower condensing temperature during cool weather.
A storage room and coil run with a larger air-to-refrigerant temperature difference.
An industrial ammonia refrigeration plant is screened at one specified load and condensing condition.
COP = Qevap / Wcomp • EER = 3.41214 × COP
These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.
TD = Tair,in − Tevap • COPCarnot = Tevap,K / (Tcond,K − Tevap,K)
TD describes the air-to-refrigerant difference at the evaporator. Carnot lift uses the two saturation temperatures, with an absolute cold-side temperature.
THR = Qevap + Wcomp • volume flow = THR / (ρ × cp × ΔT)
This screen assumes compressor input heat reaches the condenser. Air properties are 1.20 kg/m³ and 1.006 kJ/(kg·K). Water properties are 997 kg/m³ and 4.186 kJ/(kg·K).
In the modeled boundary the compressor consumes electrical power. The condenser rejects this added energy together with the heat removed from the cold room.
Subtract the saturation temperature at the evaporator from the entering room air temperature. The inlet-to-outlet air temperature change is a separate measurement.
ColdChainLab · Engineering calculation
Metric SI · https://calcsheetlab.com/coldchainlab/evaporator-td-condenser-thr-cop/
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.