Input and output at one operating point
COP = Qevap / Wcomp • EER = 3.41214 × COP
These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.
Worked example · Equipment selection
A storage room and coil run with a larger air-to-refrigerant temperature difference.
Edit any value to recalculate.
Heat absorbed at the evaporator and compressor electrical work combine at the condenser.
Review the evaporator TD separately from condenser air rise. A high TD can affect produce moisture and frost behavior.
Open a case with its assumptions loaded, then edit the inputs.
A walk-in cooler has a measured compressor input and enough airflow to evaluate a candidate condenser temperature rise.
A refrigeration plant rejects heat to a water loop with a specified supply-to-return rise.
A freezer load drives a low evaporating saturation temperature relative to the condenser.
A medium-temperature circuit runs with a lower condensing temperature during cool weather.
An industrial ammonia refrigeration plant is screened at one specified load and condensing condition.
COP = Qevap / Wcomp • EER = 3.41214 × COP
These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.
TD = Tair,in − Tevap • COPCarnot = Tevap,K / (Tcond,K − Tevap,K)
TD describes the air-to-refrigerant difference at the evaporator. Carnot lift uses the two saturation temperatures, with an absolute cold-side temperature.
THR = Qevap + Wcomp • volume flow = THR / (ρ × cp × ΔT)
This screen assumes compressor input heat reaches the condenser. Air properties are 1.20 kg/m³ and 1.006 kJ/(kg·K). Water properties are 997 kg/m³ and 4.186 kJ/(kg·K).
Review the evaporator TD separately from condenser air rise. A high TD can affect produce moisture and frost behavior.
ColdChainLab · Engineering calculation
Metric SI · https://calcsheetlab.com/coldchainlab/evaporator-td-condenser-thr-cop/high-td-storage-evaporator/
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.