Worked example · Equipment selection

Water-cooled process condenser

A refrigeration plant rejects heat to a water loop with a specified supply-to-return rise.

Actual COP
3.24
Evaporator TD
9K
Heat rejected
157kW
EER
11.07BTU/(Wh)
Edit inputs

Inputs

Edit any value to recalculate.

Capacity & electrical input
kW
kW
Operating temperatures
°C
°C
°C
Heat-rejection medium

Air and water flows are alternatives at their entered temperature rises.

K
K

Refrigeration-cycle energy flow

Refrigeration-cycle energy flowHeat absorbed at the evaporator and compressor electrical work combine at the condenser.Evaporator120 kW-11 °C saturationCompressor37 kWElectrical inputCondenser157 kW39 °C saturationExpansion valvePressure dropsLiquid to two-phaseCold-side heatHeat rejection

Heat absorbed at the evaporator and compressor electrical work combine at the condenser.

Calculation breakdown

Carnot refrigeration COP
5.24
Fraction of Carnot COP
61.9%
Condenser air volume flow
42,563m³/h
Condenser water volume flow
451.4L/min
Saturation temperature lift
50K
Net refrigeration capacity
34.12TR

Work through this case

  1. Heat rejected 157kW
  2. Condenser water volume flow 451.4L/min
  3. Fraction of Carnot COP 61.9%

Check the condenser water volume flow against heat rejection. A smaller allowable water temperature rise raises the required flow.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Input and output at one operating point

COP = Qevap / Wcomp • EER = 3.41214 × COP

These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.

Temperature difference & ideal limit

TD = Tair,in − Tevap • COPCarnot = Tevap,K / (Tcond,K − Tevap,K)

TD describes the air-to-refrigerant difference at the evaporator. Carnot lift uses the two saturation temperatures, with an absolute cold-side temperature.

Condenser heat rejection

THR = Qevap + Wcomp • volume flow = THR / (ρ × cp × ΔT)

This screen assumes compressor input heat reaches the condenser. Air properties are 1.20 kg/m³ and 1.006 kJ/(kg·K). Water properties are 997 kg/m³ and 4.186 kJ/(kg·K).

References

Questions and answers

What should I check in the water-cooled process condenser example?

Check the condenser water volume flow against heat rejection. A smaller allowable water temperature rise raises the required flow.