Freeze: mass concentration table • Burst: volume concentration table
Freeze is the onset of ice in an inhibited solution. Burst is a shutdown reference that assumes space for expansion. A ≤ marker gives the coldest applicable table bound, or the colder freeze point when the applicable freeze point is below that bound. Confirm with the selected fluid supplier.
Density, specific heat, and viscosity use offline aqueous glycol fits at the mean fluid temperature. Properties vary with inhibitor package. Flow is unavailable when the cold leg reaches the freeze point.
Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.
What is the difference between freeze protection and burst protection?
Freeze protection keeps the coolant pumpable above the first-ice temperature. Burst screening applies at shutdown, where a partly frozen solution needs space to expand.
Can I apply the displayed pressure factor to a turbulent loop?
Use it only to screen laminar pressure loss in the same geometry. For turbulent flow, use the calculated properties to find Reynolds number and recalculate friction, fittings, and coil losses.
ColdChainLab · Engineering calculation
Glycol Brine Freeze Point & Flow Calculator
Metric SI · https://calcsheetlab.com/coldchainlab/glycol-brine-freeze-flow/
Inputs
Glycol type
Propylene glycol
Concentration by weight
40 %
Mean operating fluid temp.
-5 °C
Target cooling load
45 kW
Return-to-supply rise
5 K
Results
Freeze point
-21.1°C
Burst limit
≤ -45.6°C
Required flow
142.6L/min
Laminar ΔP
17.68×
Specific heat
3.625kJ/(kg·K)
Specific-heat ratio to water
0.867×
Fluid density
1,044.5kg/m³
Specific gravity (water at 20 °C)
1.046
Required flow vs water
1.103×
Dynamic viscosity
16.07mPa·s
Same-flow laminar pressure factor
16.03×
Supply leg margin above freeze
13.6K
Estimated supply temperature
-7.5°C
Approximate volume concentration
40.2%
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.