Worked example · Secondary loops

High-concentration propylene glycol loop

A propylene glycol solution near the top of the supported concentration range is screened for pump demand.

Freeze point
-51.1°C
Burst limit
≤ -51.1°C
Required flow
222.5L/min
Laminar ΔP
171.92×
Edit inputs

Inputs

Edit any value to recalculate.

Secondary coolant

Concentration is mass percent of glycol in the solution.

%
°C
Loop duty

The cold supply leg is the mean operating temperature minus half the loop rise.

kW
K

Freeze point and flow correction

Freeze point and flow correctionThe flow correction curve starts where the estimated cold supply leg stays liquid at the selected duty.Freeze / °CGlycol concentration / wt %015304560-55-36-172Flow / ×0.951.071.191.31Freeze pointRequired flow factor

The flow correction curve starts where the estimated cold supply leg stays liquid at the selected duty.

Calculation breakdown

Specific heat
3.159kJ/(kg·K)
Specific-heat ratio to water
0.755×
Fluid density
1,066.7kg/m³
Specific gravity (water at 20 °C)
1.069
Required flow vs water
1.239×
Dynamic viscosity
139.07mPa·s
Same-flow laminar pressure factor
138.8×
Supply leg margin above freeze
28.1K
Estimated supply temperature
-23°C
Approximate volume concentration
61.1%

Work through this case

  1. Freeze point -51.1°C
  2. Dynamic viscosity 139.07mPa·s
  3. Required flow 222.5L/min

Check the colder-temperature properties and the required flow together. High viscosity can govern pump and heat exchanger sizing.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Freeze and burst protection

Freeze: mass concentration table • Burst: volume concentration table

Freeze is the onset of ice in an inhibited solution. Burst is a shutdown reference that assumes space for expansion. A ≤ marker gives the coldest applicable table bound, or the colder freeze point when the applicable freeze point is below that bound. Confirm with the selected fluid supplier.

Sensible cooling flow

L/min = 60,000 × Q(kW) / [ρ(kg/m³) × cp(kJ/(kg·K)) × ΔT(K)]

Density, specific heat, and viscosity use offline aqueous glycol fits at the mean fluid temperature. Properties vary with inhibitor package. Flow is unavailable when the cold leg reaches the freeze point.

Water-reference derating

Kflow = (ρcp)water / (ρcp)glycol • KΔP,laminar = (μglycol / μwater) × Kflow

Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.

References

Questions and answers

What should I check in the high-concentration propylene glycol loop example?

Check the colder-temperature properties and the required flow together. High viscosity can govern pump and heat exchanger sizing.