Freeze: mass concentration table • Burst: volume concentration table
Freeze is the onset of ice in an inhibited solution. Burst is a shutdown reference that assumes space for expansion. A ≤ marker gives the coldest applicable table bound, or the colder freeze point when the applicable freeze point is below that bound. Confirm with the selected fluid supplier.
Density, specific heat, and viscosity use offline aqueous glycol fits at the mean fluid temperature. Properties vary with inhibitor package. Flow is unavailable when the cold leg reaches the freeze point.
Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.
What should I check in the propylene glycol near the freeze margin example?
Check the minimum temperature at the coldest point, including startup and flow transients. A small positive modeled margin can be inadequate.
ColdChainLab · Engineering calculation
Propylene glycol near the freeze margin
Metric SI · https://calcsheetlab.com/coldchainlab/glycol-brine-freeze-flow/propylene-glycol-near-freeze/
Inputs
Glycol type
Propylene glycol
Concentration by weight
40 %
Mean operating fluid temp.
-17.5 °C
Target cooling load
27 kW
Return-to-supply rise
5 K
Results
Freeze point
-21.1°C
Burst limit
≤ -45.6°C
Required flow
86.2L/min
Laminar ΔP
42.06×
Specific heat
3.584kJ/(kg·K)
Specific-heat ratio to water
0.857×
Fluid density
1,048.9kg/m³
Specific gravity (water at 20 °C)
1.051
Required flow vs water
1.11×
Dynamic viscosity
37.95mPa·s
Same-flow laminar pressure factor
37.88×
Supply leg margin above freeze
1.1K
Estimated supply temperature
-20°C
Approximate volume concentration
40.2%
The supply temperature is within 3 K of the freeze point. Check the design margin at the lowest expected temperature.
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.