Worked example · Secondary loops

Propylene glycol near the freeze margin

A propylene glycol loop has a supply leg only slightly warmer than the onset of freezing.

Freeze point
-21.1°C
Burst limit
≤ -45.6°C
Required flow
86.2L/min
Laminar ΔP
42.06×
Edit inputs

Inputs

Edit any value to recalculate.

Secondary coolant

Concentration is mass percent of glycol in the solution.

%
°C
Loop duty

The cold supply leg is the mean operating temperature minus half the loop rise.

kW
K

The supply temperature is within 3 K of the freeze point. Check the design margin at the lowest expected temperature.

Freeze point and flow correction

Freeze point and flow correctionThe flow correction curve starts where the estimated cold supply leg stays liquid at the selected duty.Freeze / °CGlycol concentration / wt %015304560-55-36-172Flow / ×0.951.071.191.31Freeze pointRequired flow factor

The flow correction curve starts where the estimated cold supply leg stays liquid at the selected duty.

Calculation breakdown

Specific heat
3.584kJ/(kg·K)
Specific-heat ratio to water
0.857×
Fluid density
1,048.9kg/m³
Specific gravity (water at 20 °C)
1.051
Required flow vs water
1.11×
Dynamic viscosity
37.95mPa·s
Same-flow laminar pressure factor
37.88×
Supply leg margin above freeze
1.1K
Estimated supply temperature
-20°C
Approximate volume concentration
40.2%

Work through this case

  1. Freeze point -21.1°C
  2. Supply leg margin above freeze 1.1K
  3. Laminar ΔP 42.06×

Check the minimum temperature at the coldest point, including startup and flow transients. A small positive modeled margin can be inadequate.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Freeze and burst protection

Freeze: mass concentration table • Burst: volume concentration table

Freeze is the onset of ice in an inhibited solution. Burst is a shutdown reference that assumes space for expansion. A ≤ marker gives the coldest applicable table bound, or the colder freeze point when the applicable freeze point is below that bound. Confirm with the selected fluid supplier.

Sensible cooling flow

L/min = 60,000 × Q(kW) / [ρ(kg/m³) × cp(kJ/(kg·K)) × ΔT(K)]

Density, specific heat, and viscosity use offline aqueous glycol fits at the mean fluid temperature. Properties vary with inhibitor package. Flow is unavailable when the cold leg reaches the freeze point.

Water-reference derating

Kflow = (ρcp)water / (ρcp)glycol • KΔP,laminar = (μglycol / μwater) × Kflow

Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.

References

Questions and answers

What should I check in the propylene glycol near the freeze margin example?

Check the minimum temperature at the coldest point, including startup and flow transients. A small positive modeled margin can be inadequate.