Refrigerant P–T Superheat & Subcooling Calculator

Diagnose superheat and subcooling for R-448A, R-404A, R-134a, R-410A, propane and ammonia using bubble and dew points.

Superheat
7.7K
Subcooling
6.2K
Suction dew
-14.7°C
Liquid bubble
31.2°C
Edit inputs

Inputs

Edit any value to recalculate.

Refrigerant & pressure basis

For gauge readings, enter local barometric pressure. Each pressure and temperature pair should come from the same line location.

kPa(a)
Measured line conditions
kPa(g)
°C
kPa(g)
°C

Saturation pressure–temperature

Saturation pressure–temperatureThe operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.Pressure / kPa(g) (log scale)Temperature / °C-53.9-22.78.539.770.9-12068432,799SH 7.7 KSC 6.2 KDew / vaporBubble / liquid

The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.

Calculation breakdown

Suction bubble point
-20.6°C
Liquid dew point
36.2°C
Suction temperature glide
5.9K
Liquid temperature glide
5K
Absolute suction pressure
300kPa(a)
Absolute liquid pressure
1,500kPa(a)
Supported absolute pressure range
100–2,900kPa(a)

Worked examples

Open a case with its assumptions loaded, then edit the inputs.

Formulas and assumptions

Gauge and absolute pressure

Pabsolute = Pgauge + Plocal atmosphere

The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.

Superheat and subcooling

SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line

Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.

Saturation curves

P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]

The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.

References

Questions and answers

Which R-448A saturation temperature should I use?

Use the vapor dew temperature at the suction pressure for superheat and the liquid bubble temperature at the liquid pressure for subcooling. The average saturation temperature is sometimes used for equipment ratings.

Can a suction reading be below zero on a gauge?

Yes. A negative gauge value is below local atmospheric pressure. The calculator adds barometric pressure before looking up the saturation point.