The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.
Calculation breakdown
Suction bubble point
-20.6°C
Liquid dew point
36.2°C
Suction temperature glide
5.9K
Liquid temperature glide
5K
Absolute suction pressure
300kPa(a)
Absolute liquid pressure
1,500kPa(a)
Supported absolute pressure range
100–2,900kPa(a)
Work through this case
Suction temperature glide5.9K
Superheat7.7K
Subcooling6.2K
Notice the two distinct saturation temperatures at each pressure. The correct comparisons are suction dew and liquid bubble, respectively.
More worked examples
Open a case with its assumptions loaded, then edit the inputs.
The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.
Superheat and subcooling
SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line
Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.
Saturation curves
P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]
The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.
What should I check in the r-448a supermarket glide check example?
Notice the two distinct saturation temperatures at each pressure. The correct comparisons are suction dew and liquid bubble, respectively.
ColdChainLab · Engineering calculation
R-448A supermarket glide check
Metric SI · https://calcsheetlab.com/coldchainlab/refrigerant-pt-superheat-subcooling/r448a-supermarket-glide/
Inputs
Refrigerant
R-448A
Pressure reference
Absolute pressure
Suction pressure
300 kPa(a)
Suction line temperature
-7 °C
Liquid pressure
1500 kPa(a)
Liquid line temperature
25 °C
Results
Superheat
7.7K
Subcooling
6.2K
Suction dew
-14.7°C
Liquid bubble
31.2°C
Suction bubble point
-20.6°C
Liquid dew point
36.2°C
Suction temperature glide
5.9K
Liquid temperature glide
5K
Absolute suction pressure
300kPa(a)
Absolute liquid pressure
1,500kPa(a)
Supported absolute pressure range
100–2,900kPa(a)
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.