Worked example · Field diagnostics

R-404A low-temperature rack

A frozen-food rack has a low suction pressure and a separate liquid-line reading at a stable operating point.

Superheat
9.75K
Subcooling
7.23K
Suction dew
-24.75°C
Liquid bubble
33.23°C
Edit inputs

Inputs

Edit any value to recalculate.

Refrigerant & pressure basis

For gauge readings, enter local barometric pressure. Each pressure and temperature pair should come from the same line location.

Measured line conditions
kPa(a)
°C
kPa(a)
°C

Saturation pressure–temperature

Saturation pressure–temperatureThe operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.Pressure / kPa(a) (log scale)Temperature / °C-74.1-3703774.1371657263,200SH 9.7 KSC 7.2 KDew / vaporBubble / liquid

The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.

Calculation breakdown

Suction bubble point
-25.38°C
Liquid dew point
33.6°C
Suction temperature glide
0.63K
Liquid temperature glide
0.36K
Absolute suction pressure
250kPa(a)
Absolute liquid pressure
1,550kPa(a)
Supported absolute pressure range
37.4–3,200kPa(a)

Work through this case

  1. Suction dew -24.75°C
  2. Liquid bubble 33.23°C
  3. Subcooling 7.23K

R-404A glide is smaller than R-448A glide, but the model still uses separate curves for its liquid and vapor sides.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Gauge and absolute pressure

Pabsolute = Pgauge + Plocal atmosphere

The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.

Superheat and subcooling

SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line

Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.

Saturation curves

P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]

The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.