The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.
Calculation breakdown
Suction bubble point
-25.38°C
Liquid dew point
33.6°C
Suction temperature glide
0.63K
Liquid temperature glide
0.36K
Absolute suction pressure
250kPa(a)
Absolute liquid pressure
1,550kPa(a)
Supported absolute pressure range
37.4–3,200kPa(a)
Work through this case
Suction dew-24.75°C
Liquid bubble33.23°C
Subcooling7.23K
R-404A glide is smaller than R-448A glide, but the model still uses separate curves for its liquid and vapor sides.
More worked examples
Open a case with its assumptions loaded, then edit the inputs.
The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.
Superheat and subcooling
SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line
Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.
Saturation curves
P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]
The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.
What should I check in the r-404a low-temperature rack example?
R-404A glide is smaller than R-448A glide, but the model still uses separate curves for its liquid and vapor sides.
ColdChainLab · Engineering calculation
R-404A low-temperature rack
Metric SI · https://calcsheetlab.com/coldchainlab/refrigerant-pt-superheat-subcooling/r404a-low-temperature-rack/
Inputs
Refrigerant
R-404A
Pressure reference
Absolute pressure
Suction pressure
250 kPa(a)
Suction line temperature
-15 °C
Liquid pressure
1550 kPa(a)
Liquid line temperature
26 °C
Results
Superheat
9.75K
Subcooling
7.23K
Suction dew
-24.75°C
Liquid bubble
33.23°C
Suction bubble point
-25.38°C
Liquid dew point
33.6°C
Suction temperature glide
0.63K
Liquid temperature glide
0.36K
Absolute suction pressure
250kPa(a)
Absolute liquid pressure
1,550kPa(a)
Supported absolute pressure range
37.4–3,200kPa(a)
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.