ControlLoopLab
Home CalculatorsSampled signals

Digital IIR low-pass filters

Design a normalized low-pass recursion and check its cutoff, phase lag, group delay, step timing and noise bandwidth.

Model inputs

Filter specification
Hz
Hz
Hz

Discrete transfer & step samples

Below Nyquist
Cutoff gain
−3.0103dB
Test phase
−137.45°
Test delay
1.6947ms
Noise BW
44.068Hz
Discrete low-pass attenuation and step responseDiscrete attenuationdB3.3311.740.8143500−72−47−223Frequency (Hz, log)Unit-step samplesoutput0481216−0.08340.320.7231.13Sample index nCutoff markerTest markerStep samples
y[n] = b0 x[n] + b1 x[n−1] + b2 x[n−2] − a1 y[n−1] − a2 y[n−2]

Calculated results

b0
0.013359200027856503
b1
0.026718400055713007
b2
0.013359200027856503
a1
-1.6474599810769766
a2
0.7008967811884025
DC gain
1×
Cutoff attenuation
−3.0103dB
Cutoff phase
−90°
Cutoff group delay
5.6867samples
Cutoff group delay
5.6867ms
Test attenuation
−12.568dB
Test phase
−137.45°
Test group delay
1.6947samples
Test group delay
1.6947ms
95% first crossing
12ms
99% first crossing
13ms
Equivalent noise bandwidth
44.068Hz

Model and interpretation

Full methodology

Set cutoff in digital frequency

Cutoff is strictly between DC and Nyquist. EMA uses the exact digital half-power coefficient. Tustin and Butterworth prewarp the cutoff before bilinear conversion. The denominator uses a0 = 1 and the negative-feedback convention shown above.

Read phase and delay separately

Phase is ∠H(eʲω). Group delay is −d∠H/dω in samples and can differ sharply from phase delay. At a Nyquist transmission zero the displayed phase is the one-sided limit. The noise bandwidth is the one-sided integral of |H|² at unity DC.

Check how the firmware represents it

Step times show the first sample at or past 95% and 99%, with the input step at n = 0. Near DC or Nyquist, implement a suitable factored or high-precision realization and recheck coefficient quantization.