DP orifice square-root flow

An orifice transmitter outputs linear differential pressure and the host derives the flow rate.

Model inputs

Supply & wiring
V
V
Ω
Ω
m
mm²
°C
Current scaling
mA
EU
EU

Fractional AWG shows the equivalent copper area.

Two-wire circuit & voltage reserve

In range
Headroom
6.3475V
Loop load
256.93Ω
Scaled value
200EU
Input current
8mA
Two-wire circuit and transmitter voltagePowered two-wire loop22 mA checkDC supply24 VTransmitter18.3 VAI load250 ΩBarrier0 ΩCopper pair 6.93 ΩTransmitter voltage windowLift-off 12 VTX 18.3 V
VTX = Vsup − 0.022 (RAI + Rbarrier + RCu, round trip)

Calculated results

Allowable load at 22 mA
545.45Ω
Installed load
256.93Ω
Copper round-trip resistance
6.9332Ω
Transmitter terminals at 22 mA
18.347V
Compliance headroom
6.3475V
Load reserve
288.52Ω
NE 43 screening band
Normal
Scaled reading
200EU
HART 250 Ω load
Pass
  • HART uses a 250 Ω minimum DC-load screen. Confirm the modem load window and AC impedance of the complete loop.

Model and interpretation

Full methodology

Screen worst-case load

Both copper conductors count. The nominal copper model uses 0.017241 Ω·mm²/m at 20 °C and a 0.00393/°C temperature coefficient. AWG uses a continuous equivalent area so changing units keeps the same cable. Compare with the cable datasheet and actual minimum supply.

Read NE 43 bands

4–20 mA is the nominal measurement span. This screen uses ≤3.6 mA for low fault and ≥21 mA for high fault. The low guard band is above 3.6 through 3.8 mA. The high guard band is above 20.5 and below 21 mA. Verify the instrument and host configuration. A low current alone cannot distinguish a sensor fault from an open wire or power loss.

Avoid double square rooting

Select square-root scaling for signal current proportional to differential pressure. Leave it linear if the transmitter already outputs linearized flow. Values outside the live range remain mathematical readouts. Verify HART AC load and barrier approvals separately.