ControlLoopLab
Home 4–20 mA loopWorked example

Remote safety-barrier loop with low headroom

A remote transmitter with a safety barrier must stay powered at its configured high-fault output.

Model inputs

Supply & wiring
V
V
Ω
Ω
m
mm²
°C
Current scaling
mA
EU
EU

Fractional AWG shows the equivalent copper area.

Two-wire circuit & voltage reserve

Voltage budget fail
Headroom
−2.2331V
Loop load
419.69Ω
Scaled value
178EU
Input current
21.8mA
Two-wire circuit and transmitter voltagePowered two-wire loop22 mA checkDC supply19 VTransmitter9.77 VAI load250 ΩBarrier95 ΩCopper pair 74.7 ΩTransmitter voltage windowLift-off 12 VTX 9.77 V
VTX = Vsup − 0.022 (RAI + Rbarrier + RCu, round trip)

Calculated results

Allowable load at 22 mA
318.18Ω
Installed load
419.69Ω
Copper round-trip resistance
74.687Ω
Transmitter terminals at 22 mA
9.7669V
Compliance headroom
−2.2331V
Load reserve
−101.51Ω
NE 43 screening band
Fault high
Scaled reading
178EU
HART 250 Ω load
Pass
  • The scaled value is mathematical only. Treat an out-of-range or fault-band signal according to the transmitter and host configuration.
  • HART uses a 250 Ω minimum DC-load screen. Confirm the modem load window and AC impedance of the complete loop.

Model and interpretation

Full methodology

Screen worst-case load

Both copper conductors count. The nominal copper model uses 0.017241 Ω·mm²/m at 20 °C and a 0.00393/°C temperature coefficient. AWG uses a continuous equivalent area so changing units keeps the same cable. Compare with the cable datasheet and actual minimum supply.

Read NE 43 bands

4–20 mA is the nominal measurement span. This screen uses ≤3.6 mA for low fault and ≥21 mA for high fault. The low guard band is above 3.6 through 3.8 mA. The high guard band is above 20.5 and below 21 mA. Verify the instrument and host configuration. A low current alone cannot distinguish a sensor fault from an open wire or power loss.

Avoid double square rooting

Select square-root scaling for signal current proportional to differential pressure. Leave it linear if the transmitter already outputs linearized flow. Values outside the live range remain mathematical readouts. Verify HART AC load and barrier approvals separately.