Insulation Batts, Blown-In & R-Value Calculator

Estimate insulation batt packs or loose-fill bags, check added settled depth, and calculate effective R-value across cavity and framing paths.

Project inputs

Area and insulation
ft²
R
R
Product coverage
R/inLeave at 0 for the material’s planning value.
lb/ft³Leave at 0 for the material and location preset.
lbLeave at 0 for the loose-fill material preset.
ft²Enter the product chart yield to replace the density estimate.
%
Effective wall R-value check
%
R
R
View shopping list

Shopping list

50 bagsBlown-in cellulose 25 lb per bag

Insulated area
1,200 ft²
Added settled depth
8.57 in
Cavity or attic total
49 R
Effective wall assembly
18.44 R

Insulation section · relative layers Insulation section · relative layers Added · 8.57 inExisting · 19 R8.57 in added · 18.44 R effective wall rating
Schematic layout

Takeoff math

  1. Determine added thermal resistance

    19 R existing + 30 R added = 49 R. At 3.5 R/in, plan for 8.57 in added settled depth.

  2. Round to whole packages

    857.14 ft³ fill × 1.45 lb/ft³ = 1,242.86 lb before reserve. Divide by 25 lb per bag, add 0%, and round up to 50.

  3. Check the parallel wall paths

    1 ÷ ((1 − 23%) ÷ 50.5 R cavity path + 23% ÷ 5.9 R framing path) = 18.44 R.

Check before you buy

For batts, divide the measured cavity area by pack coverage. For loose fill, estimate added settled depth and use a product coverage row or a density-based volume estimate. Effective wall R-value combines heat flow through the cavity and framing in parallel.

Read the product chart for minimum installed and settled depth and minimum bags. Confirm wall or attic use, package coverage at your spacing, and the condition and depth of existing insulation.

Frequently asked questions

Why is the effective wall R-value lower than the cavity rating?

Framing typically conducts more heat than the insulated cavities. The calculation weights each path by its share of the wall area and combines their heat flow.

Do I need extra blown-in insulation if the attic already meets my target?

Target mode estimates zero added depth when the measured existing R-value meets or exceeds the target. Inspect thin or compressed spots separately before using one R-value for the whole attic.