NFPA 2001 · Worked example

FM-200 electrical room

A small electrical room uses an entered 7.0% HFC-227ea concentration. The nominal full charge is 58 lb per cylinder.

Inputs

Agent and enclosure
ft³
%

Enter the listed concentration for the fuel and system.

°F
°F
ft
lb

Use usable agent mass, including for IG-541.

Positive-pressure vent screen
s
psf
ft²

Clean-agent enclosure section

Worksheet units
Edit inputs
Clean-agent enclosure section · Input-linked engineering diagramAGENT MASS91.56lbCYLINDERS2PEAK CONC.9.06%VENT AREA0.81ft²HFC-227eaROOM 2,600 ft³2 CYLFree vent 2.2 ft²Modeled full-charge exposure9.06%0%9% NOAEL10.5% LOAEL
Exposure reference exceeded

The modeled full charge at the hot condition exceeds the no-effect screening reference.

How to read this example

Review both the effect of cylinder rounding and the estimated positive vent area at the entered enclosure limit.

Open the base calculator

Calculated values

Atmosphere-corrected design mass
91.56 lb
Specific vapor volume at design temperature
2.1374 ft³/lb
Atmospheric correction factor
1
Estimated cylinder count
2
Installed charge at full entered fill
116 lb
IG-541 free gas at 70 °F / 21 °C
Inert gas only
Installed concentration at minimum temperature
8.71 %
Installed concentration at maximum temperature
9.06 %
Equivalent oxygen at sea level
Inert gas only
No-effect exposure reference
9 %
Low-effect exposure reference
10.5 %
Margin to no-effect reference
-0.06 pp
Estimated required clear vent area
0.81 ft²
Modeled positive peak pressure
0.81 psf
Clear vent area reserve
1.39 ft²

Equations and assumptions

  • Halocarbon W = (V/S) [C/(100 − C)] × f_atm
  • IG-541 X = 2.303 (V_s/S) log₁₀[100/(100 − C)]
  • IG-541 free gas = room volume × X × f_atm
  • A_vent ≈ Q_peak / [C_d √(2 ΔP/ρ_air)]

Enter the design concentration from the listing. Required mass uses the minimum temperature and interpolated atmospheric correction. Exposure uses the full rounded cylinder charge at maximum temperature. For IG-541, the exposure bar uses sea-level equivalent oxygen expressed as equivalent agent concentration.

The exposure references screen concentration only. Honor current NFPA 2001 exposure time and egress provisions. Use the listed system design, enclosure integrity testing and the agent-specific safety data.

The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.