NFPA 2001 · Worked example

IG-541 archive enclosure

An archive enclosure has a 14,500 ft³ net volume. The calculation uses the entered 37% IG-541 design concentration and a 60-second planning discharge.

Inputs

Agent and enclosure
m³
%

Enter the listed concentration for the fuel and system.

°C
°C
m
kg

Use usable agent mass, including for IG-541.

Positive-pressure vent screen
s
Pa
m²

Clean-agent enclosure section

Worksheet units
Edit inputs
Clean-agent enclosure section · Input-linked engineering diagramAGENT MASS271.7kgCYLINDERS10PEAK CONC.40.36%VENT AREA0.43m²IG-541ROOM 410.59 m³10 CYLFree vent 1.11 m²Modeled full-charge exposure40.36%0%43% NOAEL52% LOAEL
Within entered screening limits

The modeled concentration and positive vent area clear the entered checks. Confirm listed design and exposure provisions.

How to read this example

Check the 70 °F free-gas volume and equivalent oxygen at the hot condition. Cylinder selection uses the stated discharge mass.

Open the base calculator

Calculated values

Atmosphere-corrected design mass
271.7 kg
Specific vapor volume at design temperature
0.6984 m³/kg
Atmospheric correction factor
1
Estimated cylinder count
10
Installed charge at full entered fill
294.84 kg
IG-541 free gas at 70 °F / 21 °C
192.65 m³
Installed concentration at minimum temperature
39.44 %
Installed concentration at maximum temperature
40.36 %
Equivalent oxygen at sea level
12.46 %
No-effect exposure reference
43 %
Low-effect exposure reference
52 %
Margin to no-effect reference
2.64 pp
Estimated required clear vent area
0.43 m²
Modeled positive peak pressure
42.11 Pa
Clear vent area reserve
0.69 m²

Equations and assumptions

  • Halocarbon W = (V/S) [C/(100 − C)] × f_atm
  • IG-541 X = 2.303 (V_s/S) log₁₀[100/(100 − C)]
  • IG-541 free gas = room volume × X × f_atm
  • A_vent ≈ Q_peak / [C_d √(2 ΔP/ρ_air)]

Enter the design concentration from the listing. Required mass uses the minimum temperature and interpolated atmospheric correction. Exposure uses the full rounded cylinder charge at maximum temperature. For IG-541, the exposure bar uses sea-level equivalent oxygen expressed as equivalent agent concentration.

The exposure references screen concentration only. Honor current NFPA 2001 exposure time and egress provisions. Use the listed system design, enclosure integrity testing and the agent-specific safety data.

The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.