NFPA 2001 · Worked example
IG-541 archive enclosure
An archive enclosure has a 14,500 ft³ net volume. The calculation uses the entered 37% IG-541 design concentration and a 60-second planning discharge.
Inputs
Clean-agent enclosure section
Edit inputsThe modeled concentration and positive vent area clear the entered checks. Confirm listed design and exposure provisions.
How to read this example
Check the 70 °F free-gas volume and equivalent oxygen at the hot condition. Cylinder selection uses the stated discharge mass.
Open the base calculatorCalculated values
- Atmosphere-corrected design mass
- 271.7 kg
- Specific vapor volume at design temperature
- 0.6984 m³/kg
- Atmospheric correction factor
- 1
- Estimated cylinder count
- 10
- Installed charge at full entered fill
- 294.84 kg
- IG-541 free gas at 70 °F / 21 °C
- 192.65 m³
- Installed concentration at minimum temperature
- 39.44 %
- Installed concentration at maximum temperature
- 40.36 %
- Equivalent oxygen at sea level
- 12.46 %
- No-effect exposure reference
- 43 %
- Low-effect exposure reference
- 52 %
- Margin to no-effect reference
- 2.64 pp
- Estimated required clear vent area
- 0.43 m²
- Modeled positive peak pressure
- 42.11 Pa
- Clear vent area reserve
- 0.69 m²
Equations and assumptions
Halocarbon W = (V/S) [C/(100 − C)] × f_atmIG-541 X = 2.303 (V_s/S) log₁₀[100/(100 − C)]IG-541 free gas = room volume × X × f_atmA_vent ≈ Q_peak / [C_d √(2 ΔP/ρ_air)]
Enter the design concentration from the listing. Required mass uses the minimum temperature and interpolated atmospheric correction. Exposure uses the full rounded cylinder charge at maximum temperature. For IG-541, the exposure bar uses sea-level equivalent oxygen expressed as equivalent agent concentration.
The exposure references screen concentration only. Honor current NFPA 2001 exposure time and egress provisions. Use the listed system design, enclosure integrity testing and the agent-specific safety data.
The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.