NFPA 13 · Worked example
Double-interlock preaction pipe inventory
A preaction system has two Schedule 40 runs, 8 gallons of trim and a 26 psi supervisory setting.
Inputs
Supervisory pressure fill curve
Edit inputsPreaction. Use the water-delivery criteria for the selected interlock.
How to read this example
Read the volume and air estimates. Apply the listed interlock’s delivery provisions separately from any dry-pipe allowance.
Open the base calculatorCalculated values
- Total system volume
- 728.08 L
- Pipe volume subtotal
- 697.8 L
- Free air added from 0 psig
- 1.29 m³
- Required free-air delivery
- 54.26 L/min
- Modeled fill time
- 11.09 min
- Compressor delivery reserve
- 73.16 L/min
- Selected dry-pipe volume allowance
- Timed delivery applies
- Dry-pipe volume reserve
- See delivery criteria
Pipe volume by run 4 rows
| Run | Internal boremm | Lengthm | VolumeL |
|---|---|---|---|
| 1 | 102.26 | 51.8 | 425.6 |
| 2 | 40.894 | 207.3 | 272.2 |
| 3 | 35.052 | 0 | 0 |
| 4 | 26.645 | 0 | 0 |
Equations and assumptions
V_pipe = Σ π d² L / 4V_free = V_system × P_gauge / P_atmFAD_30 = V_free / 30 + leakage
The non-dwelling dry-pipe volume screening paths are 500 gal without a quick-opening device or 750 gal with one. Larger volumes can use applicable timed delivery or listed calculation paths. Dwelling dry pipe and preaction require their own delivery criteria.
The isothermal fill starts at 0 psig with free air referenced to 14.696 psia. Use delivered compressor airflow at the target pressure and the valve manufacturer’s supervisory setpoint.
The 30-minute curve describes air restoration. Water delivery after sprinkler operation is evaluated separately.