NFPA 13 · Worked example
Small dwelling dry-pipe system
A compact dwelling dry system has one short main and a low supervisory pressure. The compressor is sized from an empty-to-pressure estimate.
Inputs
Supervisory pressure fill curve
Edit inputsDwelling dry pipe. Use the applicable timed delivery requirement.
How to read this example
The air fill may clear 30 minutes while the dwelling water-delivery provision still applies. The volume-based shortcut is disabled.
Open the base calculatorCalculated values
- Total system volume
- 51.43 gal
- Pipe volume subtotal
- 47.43 gal
- Free air added from 0 psig
- 8.42 ft³
- Required free-air delivery
- 0.68 SCFM
- Modeled fill time
- 3.51 min
- Compressor delivery reserve
- 2.12 SCFM
- Selected dry-pipe volume allowance
- Timed delivery applies
- Dry-pipe volume reserve
- See delivery criteria
Pipe volume by run 4 rows
| Run | Internal borein | Lengthft | Volumegal |
|---|---|---|---|
| 1 | 2.157 | 180 | 34.2 |
| 2 | 1.097 | 270 | 13.3 |
| 3 | 1.442 | 0 | 0 |
| 4 | 1.097 | 0 | 0 |
Equations and assumptions
V_pipe = Σ π d² L / 4V_free = V_system × P_gauge / P_atmFAD_30 = V_free / 30 + leakage
The non-dwelling dry-pipe volume screening paths are 500 gal without a quick-opening device or 750 gal with one. Larger volumes can use applicable timed delivery or listed calculation paths. Dwelling dry pipe and preaction require their own delivery criteria.
The isothermal fill starts at 0 psig with free air referenced to 14.696 psia. Use delivered compressor airflow at the target pressure and the valve manufacturer’s supervisory setpoint.
The 30-minute curve describes air restoration. Water delivery after sprinkler operation is evaluated separately.